8 - HIDDEN PARAMETERS

Pag.

15

How to set up the test function

When the panel is off
Press the S the On/Off button (for 3 seconds) > [PASS] > Press the S button
> press the Arrow Up or the Arrow Down button to display [123] > Press the S button
(Hidden parameters) > Press the Arrow Up or the Arrow Down button to select the
parameter [tSt] > Press the S button > Press the Arrow Up or the Arrow Down button
to select the desired test or sequence .
To move from one test to another interrupting the one in execution, use the Arrow Up
or the Arrow Down button.
To go out from the test function and to interrupt the test in execution, press the On/Off
button.

Parameters ti.H & ti.L - timer

Functioning time="ti.H" corresponds to the thousands

"ti.L" corresponds to the units

The timer resolution is 1 hour.

How to display the parameter ti.H

When the panel is off
Press the S the On/Off button (for 3 seconds) > [PASS] > Press the s button
> [0] > Press the Arrow up or the Arrow down button to display the number [123] >
Press the S button > [C10] > Press the Arrow Up or the Arrow Down to display the
parameter [ti.H] > Press the S button > It displays the thousands value > Press the S
button to go out

How to display the parameter [ti.L]

Test with a Compact/Split unit
Test ALL [ALL]

The test ALL sets up the tests sequence t1-t2-t3-t4-t5.

Test N° 1 [t1]

It sets up the fan and commutes the four speeds to a sequence (20 seconds for each
one). The abbreviations [F1],[F2],[F3],[F4] appear on the display.

Test N° 2 [t2]

It switches on the sea water pump for 5 minutes. The message [t.P] appears on the
display.

Test N° 3 [t3]

It sets up the fan at medium speed (F2), the pump and the compressor for 5 minutes.
The message [t.C] appears on the display.

Test N° 4 [t4]

It switches on and off three times the valve/resistance relay (once per second). Then
it sets up the fan at medium speed (F2) and switches on again the valve/resistance
relay for 5 minutes. During the test the message [t.H] appears on the display.

Test N° 5 [t5]

It switches on all the warning lights and all the display segments.

When the panel is off
Press the S the On/Off button (for 3 seconds) > [PASS] > Press the S button
> Press the Arrow Up or the Arrow Down button to display [123] > Press the S button
> [C10] > Press the Arrow Up or the Arrow Down to display the parameter [ti.L] > Press
the S button > It displays the units value > Press the S button to go out
For example:
If ti.H=3
and ti.L=245
The running hours are 3245.

Summary of Contents for CLIMMA VEGA MK II

Page 1: ...A MK II Cod I1433 20 04 06 S p A COMPANY WITH QUALITY SYSTEM CERTIFIED BY DNV ISO 9001 2000 Via Cantore 6 8 20034 Giussano MI ITALY Tel 0362 35321 fax 0362 852995 info veco net E mail INSTALLATION USE...

Page 2: ...utton 2 2 S button 2 3 Arrow Up Arrow Down buttons 2 4 Display 2 5 Functioning warning lights 2 6 Probes 3 SETTING OUT 3 1 Set Point Default 25 C 3 2 Functioning Modes Default A 3 3 Fan Mode Default A...

Page 3: ...30 LSI Parameter C40 Parameter C50 Default 5 Parameter C60 Default 30 minutes Test with a Fan Coil unit Test with a Compact Split unit Parameters ti H ti L timer INDICE Pag INDICE 9 DESCRIPTION OF PAR...

Page 4: ...l unit It is a digital panel that can set up both Fan Coil units and Compact and Split units because it recognizes automati cally the system to which it is connected You can identify the unit model th...

Page 5: ...n many pieces of furniture or behind doors 3 In areas next to heat springs for example near incandescent lamps In case of anomalies during the functioning due to the panel position you have to use the...

Page 6: ...pressed by 5 seconds to save the new value 2 3 Arrow up Arrow Down buttons They have got three functions 1 When the panel is on they let enter directly the menus respectively Arrow Up for SET and Arr...

Page 7: ...ater temperature is too cool Auto It indicates that the fan control is in Automatic Mode In this case the Vega MK II panel controls the fan speed increasing or decreasing it automatically to reach and...

Page 8: ...ample C95 3 Real temperature felt by the probe 25 C Changed and displayed temperature 25 3 22 C Parameter C96 It is the external probe offset This parameter is used to change the temperature felt by t...

Page 9: ...tton SET Press the S button Press the Arrow Up or the Arrow Down button to select the desired temperature Press the S button to record it With the remote control device Press the button to increase th...

Page 10: ...ss the Arrow Up or the Arrow Down button to select A Press the S button With the remote control device Press the A button Setting out parameters Parameter C10 Differential Default 1 C How to change th...

Page 11: ...ambient temperature If the temperature decreases below 15 C the system stops and waits for a new cycle The Dehumidify cycle can not work with Fan Coil units if the circuit water is not cool How to se...

Page 12: ...on Press the Arrow Down button Fan Press the S button Press the Arrow up or the Arrow Down button to select the desired speed 1 2 3 4 Press the S button With the remote control device Press more time...

Page 13: ...parameter controls if possible the fan functioning when the Set Point is rea ched With CO5 ON the fan continues to work With CO5 OFF the fan stops How to set the parameter CO5 Default d When the panel...

Page 14: ...nctioning or inactivity recording Default Yes How to set up the Autostart function When the panel is off Press the S button CO1 Press the Arrow Down button to select CO6 press the S button Press the A...

Page 15: ...above 25 C 7 3 Message nor The abbreviation C FL suggests the user to clean the filter 2500 running hours How to reset the message C FL When the panel is on Press the S button for 3 seconds SET Press...

Page 16: ...from Cool to Heat Mode 23 C How to modify the parameter C40 When the panel is off Press the S button the Off button for 3 seconds PASS Press the S button 0 Press the Arrow Up or the Arrow Down button...

Page 17: ...ed to test all the functioning modes Different components and functioning modes are tested in order independently from the temperature felt by the thermostat Test with a Fan Coil unit Test ALL ALL Whe...

Page 18: ...displays the thousands value Press the S button to go out How to display the parameter ti L Test with a Compact Split unit Test ALL ALL The test ALL sets up the tests sequence t1 t2 t3 t4 t5 Test N 1...

Page 19: ...9 DESCRIPTION OF PARAMETERS Pag 16 9 1 Parameters table...

Page 20: ...9 DESCRIPTION OF PARAMETERS Pag 17...

Page 21: ...9 DESCRIPTION OF PARAMETERS Pag 18...

Page 22: ...9 DESCRIPTION OF PARAMETERS Pag 19 9 2 General vision of parameters...

Page 23: ...utton n 3 It decreases the Set point value Button n 4 Fan speed control Four manual speeds 1 2 3 4 or automatic speeds Button n 5 special modes Unattended Dehumidify or Fan Only Button n 6 On Off butt...

Page 24: ...supplied the warning lights are blinking and the cable is unblemished and correctly inserted call the assistance service for a more precise control 11 2 Display shows nPr The powerboard has not correc...

Page 25: ...www climma it W IN S AKE W S R L S p A Via General Cantore 6 8 20034 Giussano MI Italia C F 06633500159 P IVA 00832290969 Tel 39 0362 35321 Fax 39 0362 852995 E mail info veco net...

Reviews: