7.5 Message [NA]
The message [nA] (not Available) appears on the display when the Vega MK II is con-
nected to a Compact/Split unit of the CO type (Cool Only) and it is necessary to heat
the environment.
7 - ALARMS / MESSAGES
Pag.
12
The message [n.Pr] appears when the dip switch of the powerboard is not set out (see
Chapter 2: 2.2) or because of datas communication problems between the power-
board and the Vega MK II panel and if the CHANGE OVER is not connected.
7.4 Message [n.Pr]
In Dehumidify Mode, when the Vega MK II is connected to a Fan Coil unit.
The circuit water is above ) 25° C.
7.3 Message [nor]
The abbreviation [C.FL] suggests the user to clean the filter (2500 running hours).
How to reset the message [C.FL]
When the panel is on
Press the S button (for 3 seconds) > [SET] > Press the Arrow Down button to select
[r.ti] (reset timer) > Press the S button > Press the Arrow Up or the Arrow Down but-
ton to select [Yes] > Press the S button
7.1 HP Alarm
7.2 Message [C.FL]
ONLY when the Vega MK II is connected to a Compact/Split unit.
You can see a point on the right of the display. When the high pressure switch springs
shut for the third time, the abbreviation [HP] appears on the display and the system
stops.
You must switch off and on the panel (with the On/Off button or by the remote-control
device) to cancel the alarm signal and set up again the unit.