Veco SpA 

Installation Manual 

Page 10 / 13 

 

Main menu different pages can be scrolled down by using the ARROW UP and ARROW DOWN. To 
access the menu voice, just press the menu button. 
By pressing the HOME symbol, you can always go back to the main initial screen. 

 

MODES 

This Menu allows you to change the Mode of operation among 6 different 
possibilities: 

 

AUTO 

 this is the standard mode. In this mode the display 

automatically selects the correct functioning mode to reach (or 
keep) the Set-point temperature.  

 

FAN ONLY 

 

In this mode, the display runs the fan only (if it’s a 

Compact, the compressor will not start). 

 

DEHUMIDIFY 

 In this mode the functioning of the unit is divided 

into 3 phases: 

o

 

30 minutes in Fan Only 

o

 

Cool Mode for 30 up to 60 minutes long (parameter C60) 

o

 

Unit OFF until the new cycle starts after 6 hours. 

 

COOL ONLY 

 The unit works only in cool mode. 

 

HEAT ONLY 

 The unit works only in heat mode. 

 

SCHEDULE 

 In this mode, the system will work based on the 

scheduled of the selected program (see Chapter 2.4 for more). 

 

LANGUAGE, DATE, TIME 

This  screen  allows  modifying  language,  time  and  date;  pressing  on  the 
item that needs to be change to access the detailed screen. 
 

 

DISPLAY SETTINGS 

This screen allows modifying screen interfaces, colors and brightness. 

 

Brightness: the display has 6 levels of brightness that can be 
manually adjusted (default is maximum brightness) 

 

Screen saver: the display can be set to have no screen saver, a 
black screen saver, or a screen saver with Climma logo; also the 
screen saver time can be adjusted (from 1 up to 10 minutes).  

 

Screen colors: the display has 2 different coloring; the default is the 
dark coloring, but also a light colors is available. (available from 
version 1.1 up) 

 

Main screen layout: available from version 1.1 up) 

 

Main screen layout: the display has 2 interfaces available as main 
screen, both with the same functionalities, which can be selected 
from here: standard interface, and enhanced interface (bigger 
icons). 

Summary of Contents for Climma C-TOUCH

Page 1: ...Installation usage and maintenance manual C TOUCH CONTROL Rev 2 230511...

Page 2: ...4 2 Installation 5 2 1 Climma C Touch display location 5 1 1 Cut out and display mounting 5 1 2 Battery 6 1 1 Battery change 6 2 Operating instructions 7 2 1 Home screen and symbols 7 2 2 Initial sett...

Page 3: ...e Mk3 and EF with MK3 electronic control and with Climma fancoils with Mv8 electronic control and MCON electronic control C TOUCH can fully replace Mk3 controls and Mk2 controls considering that the M...

Page 4: ...he recommendations of this manual are solely the responsibility of the unit operator before installation and maintenance operations disconnect the unit from the power supply failure to comply may resu...

Page 5: ...erature therefore it s suggested to install it at the mid height of the cabin on an inside wall that provides a good air circulation The Climma C Touch display should not be installed in a position wh...

Page 6: ...d battery type is CR2032 The battery is used only when the panel is powered off the battery will last for a minimum of 2 years when powered off When the battery dies you need to change it and then res...

Page 7: ...ss to turn ON or OFF the fan Automatic mode when fan is in Auto mode the A is displayed on the screen 6 The bars are showing the actual fan speed through blue or red in case of heating bars 7 The symb...

Page 8: ...has to be set depending on the system it needs to control At first startup please select the language it may be changed also later on from the Main Men The display will automatically recognize if it s...

Page 9: ...an see it from its code as it containes the heater W value in the description e g MEVA7EJ FAN COIL EVA 7 DRY PAN J RES 1300W has a 1 3kW heater 2 3 Main menu The main menu is accessible through the ma...

Page 10: ...nit works only in heat mode SCHEDULE In this mode the system will work based on the scheduled of the selected program see Chapter 2 4 for more LANGUAGE DATE TIME This screen allows modifying language...

Page 11: ...rtup see 2 2 Initial settings at first start up Modbus address from this screen you can change the Modbus address of the electrical board only for fancoils with MV8 control Celsius Farenheit from this...

Page 12: ...o to the Main Menu MAIN MENU MODE SCHEDULE From the main Scheduler screen you can Turn the Scheduler ON or OFF or access one over the 6 programs to select them check how they are configured or modify...

Page 13: ...grammed correctly then the change over probe maybe faulty ERROR 2 Communication timeout ERROR 3 External alarm ERROR 4 Clean filter alarm This is a warning that comes every 2500 running hours and it s...

Reviews: