28
AW DX
Appendix A
GB
Technical data
Type
AW DX22
AW DX42
Power supply
230 V
230 V
Current max.
A
0.6
0.95
Air volume
m³/h
2000
3500
Sound pressure level
1)
dB(A)
52
62
Max. operating pressure
MPa
4.15
4.15
Inner volume coil
liter
2.3
3.7
Pipe connection coil, liquid/gas
Ø
3/8” - 5/8”
3/8” - 5/8”
Condensation drain
G1/2”
G1/2”
Max. ambient temperature
°C
40
40
Refrigerant
R410A
R410A
Protection class
IP44
IP44
Weight
kg
48
63
1)
Measured 5 metres in front of AW unit.
Air in
°C
Condensation temp
°C
AW DX22 heating output kW
AW DX42 heating output kW
15
45
11.1
19.2
20
45
9
15.8
Capacity AW DX22/DX42, heating and cooling
Air in
°C
Evaporation temp.
°C
AW DX22 cooling output kW
AW DX42 cooling output kW
27 °C DB/19 °C WB
5
9.2
16.1
Dimensions
A mm
B mm
C mm
D mm
E mm
F mm
G mm
∅
H mm
AW DX22
740
670
510
270
780
420
515
10
AW DX42
920
875
510
270
780
550
700
10