2

AC25

Operation

Air is drawn in at the top of the unit and blown out 

downwards so that it shields the door opening and mi-

nimizes heat loss. To achieve the optimum curtain effect 

the unit must extend the full width of the door opening. 

The grille for directing exhaust air is adjustable and is 

normally angled outwards to achieve the best protection 

against incoming cold air. 

The efficiency of the air curtain depends on the air 

temperature, pressure differences across the doorway and 

any wind pressure. 

NOTE! Negative pressure in the building considerably 

reduces the efficiency of the air curtain. The ventilation should 

therefore be balanced. 

Mounting

The air curtain unit is installed horizontally with the 

supply air grille facing downwards as close to the door as 

possible. Minimum distance from outlet to floor for elec-

trically heated units is 1800 mm. For other minimum 

distances, see fig. 4.

 

Mounting with wall brackets (fig. 6)

1.   Mount the brackets on the wall, see fig.6A and         

  dimension drawing fig.1. If the wall is uneven the       

  brackets must be compensated for this.

2.  Hook on the unit at the lower edge of the brackets.  

 (Fig.6B-C)

3.  Bend the top of the console over the unit and slide

    the unit's screws along the rail into the slots on the 

  consoles, (Fig.6D). When the bracket is bent once, 

  it must be replaced if bent back more than 45 °.

4.  Lock the nuts against the brackets. (Fig.6E)

 

Horizontal mounting on the ceiling 

Threaded rods, hanging brackets and ceiling mounting 

brackets for ceiling mounting are available as accessories, 

see accessories pages and separate manuals.

 

Assembly and operating instructions

Safety

•  For all installations of electrically heated products 

should a residual current circuit breaker 300 mA for 

fire protection be used.

•  Keep the areas around the air intake and exhaust gril-

les free from possible obstructions!

•  CAUTION! During operation the surfaces of the unit 

can be hot!

•  The unit must not be fully or partially covered with 

clothing, or similar materials, as overheating can result 

in a fire risk! (E)

•  The appliance can be used by children, aged from 8 

years and above, and by persons (children included) 

with reduced physical, sensory, or mental capabilities, 

or lack of experience and knowledge, if they have been 

given supervision or instruction concerning use of the 

appliance in a safe way and understand the hazards 

involved.  

Children shall not play with the appliance.  

Cleaning and user maintenance shall not be made  

by children without supervision.  

Children, of less than 3 years of age, should be kept 

away unless continuously supervised.  

Children, aged from 3 years and less than 8 years, 

shall only switch on/off the appliance, provided that 

it has been placed or installed in its intended normal 

operating position and they have been giving supervi-

sion or instruction concerning use of the appliance in a 

safe way and understand the hazards involved. 

Children, aged from 3 years and less than 8 years, 

shall not plug in, regulate and clean the appliance or 

perform user maintenance.  

General Instructions

Read these instructions carefully before installation  

and use. Keep this manual for future reference.

The product may only be used as set out in the  

assembly and operating instructions. The guarantee  

is only valid if the product is used in the manner inten-

ded and in accordance with the instructions.

 

Application area

The AC25 air curtain unit is supplied with electrical 

heating or hot water heating. AC25 is intended for 

installation heights up to 2.5 metres.

Protection class for units with electrical heating: IP20. 

Protection class for units with water heating: IP21. 

Summary of Contents for AC25

Page 1: ...AC25 Art nr 172785 01 GB Installation and maintenance instruction for air curtains IMPORTANT Read these instructions before the product is installed and used Save the instructions for future use 2 ...

Page 2: ...ircuit breaker 300 mA for fire protection be used Keep the areas around the air intake and exhaust gril les free from possible obstructions CAUTION During operation the surfaces of the unit can be hot The unit must not be fully or partially covered with clothing or similar materials as overheating can result in a fire risk E The appliance can be used by children aged from 8 years and above and by ...

Page 3: ...n to a closed water heating system The heating coil must not be connected to a mains pressure water system or an open water system Note that the unit shall be preceded by a regulating valve see valve kits The water coil is connected on the upper side of the unit with ø15 mm smooth copper pipe with a suitable coup ling or soldering The connections to the heating coil must be equipped with shut off ...

Page 4: ... Overheating The air curtain unit with electric heater is equipped with an overheat protector If it is deployed due to overheating reset as follows 1 Disconnect the electricity with the fully isolated switch 2 Determine the cause of overheating and rectify the fault 3 Remove the front hatch 4 Press the red button located inside the air curtain unit at the inner gable of the connection box 5 Reatta...

Page 5: ...water is heated enough If the fault cannot be rectified please contact a qualified service technician Residual current circuit breaker E When the installation is protected by means of a residual current circuit breaker which trips when the appliance is connected this may be due to moisture in the heating element When an appliance containing a heater element has not been used for a long period or s...

Page 6: ...7 5 ø32 5 ø25 5 ø20 5 ø17 5 Gland Knock out Knock out Knock out Gland Fig 1 Fig 2 Gland 145 345 40 183 78 165 40 1025 1535 2025 20 210 10 145 min 500 min 500 min 500 145 62 40 22 Cu ø15 min 500 min 500 145 145 2 m W E ...

Page 7: ...7 AC25 Fig 3 Open the unit A B TX20 C ...

Page 8: ...8 AC25 Fig 4 Minimum distance min 60 Minimum distance ...

Page 9: ...9 AC25 Fig 6 Mounting with wall brackets min 500 mm Mounting with wall brackets A B D E 20 35 75 210 33 ø8 3x ø5 ø10 162 C AC25 10 2 pcs AC25 15 2 pcs AC25 20 2 pcs ...

Page 10: ... AC25 15 Threaded rods for ceiling mounting Used with ceiling mounting brackets PA2PF PA34TR20 Threaded rods for 2 meter unit Length 1 m Units 6 pcs AC25 20 PA2P15 Pendulums for 1 and 1 5 meter unit Length 1 m Units 2 pcs AC25 10 AC25 15 Pendulum brackets for mounting the unit suspended from the ceiling The pendulum brackets are covered by a white plastic duct to hide the cables The brackets may b...

Page 11: ... unit PLSDC door switch and 2 modular cables with RJ12 quick connects 1 pc 3 m 1 pc 5 m IP30 PLSRTX External room temperature sensor 70x33x23 mm SIRECJ4 RJ11 coupler 4 4 Used to join together two RJ11 or RJ12 connec tors SIRECJ6 RJ12 coupler 6 6 SIRECC403 RJ11 modular cable 4 4 Length 3 m SIRECC405 Length 5 m SIRECC410 Length 10 m SIRECC415 Length 15 m SIRECC603 RJ12 modular cable 6 6 Length 3 m S...

Page 12: ...wer C2 high power L2 PE L1 L N L3 400V 3N ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection PLSB2 Over heat C cut out PL2510E08 PL2515E12 PL2520E16 C4 C3 L2 PE L1 L3 400V 3 C1 low power C2 high power M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m version C3 Run C2 Lo C1 Mid ...

Page 13: ...1 F2 F3 H1H2 Heating Motor trafo ID pot ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection PLSB2 PL2510W PL2515W PL2520W M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m version C3 Run C2 Lo C1 Mid ...

Page 14: ... Brown C Lo Mid Run Right motor L N PE N N F1 F2 F3 H1H2 Heating Motor trafo ID pot ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection PLSB2 N F1 F2 F3 OUT PA2MLK C NC NO M Blue Black Brown C Lo Mid Run Left motor Only 2 m version M C ...

Page 15: ...ent see manuals for PLS 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY PLSB2 PLSRTX optional PLSUB1 230V 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY PLSB2 PLSB2 PLSRTX optional PLSUB1 ...

Page 16: ...16 AC25 PLS Basic AC25 W C C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY 230V PLSB2 SD3a0 PLSRTX optional PLSUB1 SD230 ...

Page 17: ... C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY PLS Basic Parallel connection AC25 W Wiring diagrams for PLSAC Competent see manuals for PLS ...

Page 18: ...tt 556138 3166 VAT no SE556138316601 Postal Cheque Service 48 51 08 5 Bank Transfer 926 0365 Fax Int 46 451 410 80 E mail veab veab com Phone Int 46 451 485 00 Website www veab com NB We reserve us from typographical errors and the right to make changes and improvements to the contents of this manual without prior notice AC25 18 ...

Reviews: