MC2-FC mode FC
Document no.:200064
Version: 1.5
Page 27 of 44
Nr
Description
Range
Unit
Default
Relay assignment
5
P 951
Function solenoid valve to relay
0 = No relay assigned
1 = Ry1 on controller
2 = Ry2 on controller
3 = Ry3 on controller
4 = Ry4 on controller
5 = Ry5 on controller
6 = Ry1 on extension module
7 = Ry2 on extension module
8 = Ry3 on extension module
9 = Ry4 on extension module
10 = Ry5 on extension module
11 = Ry6 on extension module
12 = Ry7 on extension module
13 = Ry8 on extension module
14 = Ry9 on extension module
15 = Ry10 on extension module
16 = Ry11 on extension module
17 = Ry12 on extension module
0..17
-
0
P 952
Function suction valve to relay
0..17
-
0
P 953
Function off-cycle defrost to relay
0..17
-
0
P 954
Function electrical defrost evaporator 1 to relay
0..17
-
0
P 955
Function hotgas defrost evaporator 1 to relay
0..17
-
0
P 956
Function cooling ventilation to relay
0..17
-
0
P 957
Function automatic ventilation to relay
0..17
-
0
P 958
Function heating to relay
0..17
-
0
P 959
Function alarm to relay
0..17
-
1
P 960
Function electrical defrost evaporator 2 to relay
0..17
-
0
P 961
Function hotgas defrost evaporator 2 to relay
0..17
-
0
P 962
Function pressure equalisation to relay
(relay is activated P526 seconds before the first cooling action
after a hotgas defrost; relay deactivates when hotgas defrosting
is requested)
0..17
-
0
P 963
Function collect hotgas defrost to relay
(relay is activated if hotgas defrost evaporator 1 or hotgas
defrost evaporator 2 is active)
0..17
-
0
P 964
Function humidify to relay
0..17
-
0
Software / productie
P 991
Software version number
-
-
-
P 992
Serial number
-
-
-
P 993
Production date
-
year.week -
5
Multiple functions can be assigned to the same relay – for example, cooling ventilation (P956) and automatic ventilation
(P957) on the same relay.