Operation Manual
Document nr. : 053682
Version : V1.1
MC 795D
Client : General
Page : 7 of 16
Number
Description
Range
Value
Default
Setting of the alarm
P 41
P 42
P 43
P 44
P 45
P 46
P 47
P 48
P 49
Type humidity alarm
0 = No alarm
1 = Absolute alarm
2 = Relative to setpoint
Minimum alarm value
Maximum alarm value
Minimum alarm delay
Maximum alarm delay
Humidity control off
during minimum alarm
Humidity control off
during minimum alarm
Humidity control off
if all sensors at fault
Control off during external alarm
0..2
-100..+100
0..+100
0..99
0..99
0 = no
1 = yes
0 = no
1 = yes
0 = no
1 = yes
0 = no
1 = yes
-
% RH
% RH
minutes
minutes
-
-
-
-
1
0.0
+100.0
0
0
0
0
0
0
Display and setpoint
P 51
P 52
P 53
P 55
Minimum setpoint value
Maximum setpoint value
Read-out per 0,1% RH
Offset night shift
0.0..+100.0
0.0..+100.0
0 = no
1 = yes
-15..+15
% RH
% RH
-
% RH
0.0
+100.0
0
0.0
Setting analog outputs
P 61
P 62
P 63
P 64
P 65
P 66
P 71
P 72
P 73
P 74
P 75
P 76
Function analog output 1
0 = Average control temp.
1 = Setpoint
2 = P(I) dehumidifying
3 = P(I) humidifying
0 V out at
10 V out at
Proportional band
Offset prop. band
Intergral value
(999 gives only P)
Function analog output 2
0 = Average control temp.
1 = Setpoint
2 = P(I) dehumidifying
3 = P(I) humidifying
0 V out at
10 V out at
Proportional band
Offset prop. band
Intergral value
(999 gives only P)
0..3
-100..+100
-100..+100
0.1..15
-15..+15
1..999
0..3
-100..+100
-100..+100
0.1..15
-15..+15
1..999
-
-
-
-
-
minutes
-
-
-
-
-
minutes
0
0.0
+100.0
1.0
0.0
999
0
0.0
+100.0
1.0
0.0
999
Production details
P 91
P 92
P 93
Software version number
Serial number
Production date
-
-
-
-
-
year/wk
-
-
-