3

Control of the thermostat.

Normally the displays show the measured humidity and the selected setpoint.

Switching the thermostat on and off.

With the 

ON/OFF

 key the MC 795D can be switched on and off. Is the hygrostat switched off, all

displays are off. No control function is active.

Select and change humidity setpoint.

With the 

UP

 and 

DOWN

 keys the desired setpoint can be selected. The LED's next to the

setpoint display indicate which setpoint is shown.
By pushing the 

SETPOINT

 key, the setpoint starts flashing. With the 

UP

 and 

DOWN

 keys the

setpoint can be changed. By pressing the 

SETPOINT

 key again, the new setpoint is accepted.

Read-out and switching sensors on and off.

By pressing the 

SENS

 key the humidity of the first sensor is shown in the upper display.

The lower display shows the number of the sensor and of the sensor is switched on or off. 'S1on'
means that the humidity of sensor 1 is shown and that the sensor is switched on.
Sensors that are switched on are used for the control, switched off sensors not. If more sensors
for a hygrostat are switched on, the control is based on the average of those sensors.
If during the read-out of a sensor is pressed on the 

SETP

 key, a sensor can be switched on or

switched off.
By pressing the 

SENS

 key once again, the next sensor is shown. After all sensors are shown,

the average measured humidity and the setpoint are shown in the display.

Reset the alarm.

As soon as an alarm situation occurs and an error message appears on the display can, by
pressing the 

RESET ALARM

 key, the alarm be reset.

The error message remains in the display, until the cause of the error is solved.

Day/night input.

If the 

NIGHT

 input is closed, the MC 795D turns to the night mode. The 

NIGHT

 LED will light.

The setpoints are increased with the night offset.

External alarm input.

If the external alarm input is closed, an alarm message “FE” appears in the display. The alarm

relay is activated. By pressing the 

RESET ALARM

 key, the alarm be reset. The error message

remains in the display, until the cause of the error is solved.

Summary of Contents for MC 795D

Page 1: ...t Doc nr 053682 Type MANUAL Number of pages 16 Version V1 1 File Do053621 wpd Software MC795D Version V1 03 By HN Date 08 02 2007 VDH Products BV Roden Holland Signed File Doc 05 MC 795D Operating Man...

Page 2: ...liability for eventual mistakes or errors and has the right to change this document without notice Table of contents 1 Technical specifications 3 2 Functional specifications 4 3 Control of the thermo...

Page 3: ...230 Vac 50 60 Hz 10 5 Used power 9 VA Store temperature 20 60 C Operation temperature 20 50 C Operating rel humidity 10 90 RH not condensing Accuracy 0 5 of the range Front Display 4 number digital di...

Page 4: ...ve 2 Functional specifications To the MC 795D hygrostat a maximum of four humidty sensors can be connected These sensors can be used as control sensor info sensor or alarm sensor A maximum for four di...

Page 5: ...ty of sensor 1 is shown and that the sensor is switched on Sensors that are switched on are used for the control switched off sensors not If more sensors for a hygrostat are switched on the control is...

Page 6: ...e Parameter table Number Description Range Value Default Function of the hygrostat P 01 Function hygrostat 0 1 setp 1 relay D 1 1 setp 2 relay D21 2 2 setp 2 relay D22 3 1 setp 3 relay D31 4 3 setp 3...

Page 7: ...P 53 P 55 Minimum setpoint value Maximum setpoint value Read out per 0 1 RH Offset night shift 0 0 100 0 0 0 100 0 0 no 1 yes 15 15 RH RH RH 0 0 100 0 0 0 0 Setting analog outputs P 61 P 62 P 63 P 64...

Page 8: ...difying differential dehumidifying and switches off if the humidity is below setpoint offset dehumidifying The heating switches on if the humidity is lower than the setpoint offset humdifying differen...

Page 9: ...the Internal Parameters the control will stop or continue An alarm can be caused by Humidity alarm rLO Minimum alarm humidity rHI Maximum alarm humidity External alarm FE External alarm Sensor failure...

Page 10: ...NO and 1 YES Parameter table Number Description Range Value Default General A 001 A 002 A 003 A 004 Advanced programming active Software version number Serial number Production date 0 1 year wk 0 Numb...

Page 11: ...grostat 2 4 10 hygrostat 3 4 11 hygrostat 1 2 3 12 hygrostat 1 2 4 13 hygrostat 1 3 4 14 hygrostat 2 3 4 15 hygrostat 1 2 3 4 Relay 3 Relay 4 Relay 5 0 15 0 15 0 15 0 15 1 1 1 1 Function of hygrostats...

Page 12: ...um alarm Control off at maximum alarm Humidity control off if all control sensors at fault Humidity control off at external alarm 0 2 100 100 0 100 0 99 0 99 0 1 0 1 0 2 100 100 0 100 0 99 0 99 0 1 0...

Page 13: ...onal band Offset proportional band Integral value 999 P Differential value 0 19 100 100 100 100 0 1 15 15 15 1 999 0 999 minutes minutes 0 0 0 100 0 1 0 0 0 999 0 Analog output 2 A 820 A 821 A 822 A 8...

Page 14: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 14 of 16 9 Front views Front view MC 795D wall mount drawing 981714 Front view MC 795D panel mount drawing 981700...

Page 15: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 15 of 16 10 Connection diagrams Connection diagram MC 795D wall mount drawing 981715...

Page 16: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 16 of 16 Connection diagram MC 795D panel mount drawing 981702...

Page 17: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 17 of 16 11 Dimensions Dimensions wall mount drawing 940024...

Page 18: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 18 of 16 Dimensions Panel mount drawing 961271...

Reviews: