Doc. nr. : 012257
Version:
V1.9
Date:
16-02-2011
VDH Products B.V.
Type:
MANUAL FC500-PC
Page:
27 of 43
No
Name
Range
Unit
Default
P40
Frequency control mode
50 = freq/voltage controlled Max 50 Hz
51 = Voltage controlled 50 Hz
60 = freq/voltage controlled Max 60 Hz
61 = Voltage controlled 60 Hz
50-61
-
51
P41
Maximum fan speed
1..6
-
6
P42
Minimum fan speed for heat
1..6
-
1
P43
Fan startup time at max speed
0..60
Sec.
0
P51-66 see below
P70
Night temperature offset (lowers setpoint)
-10..10
C
-18..18
F
C/
F
0
P71
Night fan speed
0..6
-
0
P72
Night display mode
0..20
-
0
P75
Minimum adjustable temperature setpoint
9..29
C
48..84
F
C/
F
9
C
48
F
P76
Maximum adjustable temperature setpoint
9..29
C
48..84
F
C/
F
29
C
84
F
P80
Fan speed automatic during cooling
0=no, 1=yes
-
1
P81
Offset P-Band auto-fanspeed
-10..10
C
-18..18
F
C/
F
0
C
P82
P-Band auto-fanspeed
1,0..50,0
C
1,8..90,0
F
C/
F
2,5
C
P83
I-Time auto-fanspeed
0..999
Min.
0
P84
Frequency at 0%
20..60Hz
Hz
20Hz
P85
Voltage output at 0%
0..230V
V
93V
P86
Frequency at 100%
20..60Hz
Hz
60Hz
P87
Voltage output at 100%
0..230V
V
226V
P88
Pulse pause cycle time
0..60
Min.
5
P89
Pulse pause percentage
0..100
%
100%
P90
Network number
1..250
-
1
P91
Master/Slave number (see below)
0 = Master, 1..8 = Slave 1..8
0..8
-
0
P92
Log interval (0 = Off)
1..20
Min.
0
P93
RS485 mode selection
0 =Alfanet, 1=Modbus
0..1
-
0
P95
Software version
-
-
-
P96
Production year
P97
Production month
-
-
-
P98
Serial number
-
-
-
Setting Master/Slave configuration (P91):
For setting Master/Slave configuration you have to use a 4-button Display-unit (FC400-type (at the Display
connector)). Connect the Display to the unit you want to set.
Set one unit as Master (P91=0) and the other FC500-units to Slave (P91=1 ... 8), mind that each unit must have
a unique number.
To control the Master/slave configuration you need at least one 4-button Display-unit or one 3-button Display-
unit.