Doc. nr. : 012257
Version:
V1.9
Date:
16-02-2011
VDH Products B.V.
Type:
MANUAL FC500-PC
Page:
8 of 43
TECHNICAL DATA
:
FC 500-PC 230 Vac
Power supply voltage
: 180Vac .. 245Vac
Power supply frequency
: 50/60Hz
On/Off switch before FC500-PC
: min. 10A
Power supply cable
: 2,5mm² (14 AWG) flexible or solid wiring stripped 9mm.
Fan-control output
: 80 Vac .. 230Vac (20..50 or 20..60 Hz)
Maximal load fan-control output
: 500VA (Max. 2,2 Amp).
Water valve output
: 230Vac
Chill chaser (heater)
: 230Vac
Internal fuses
: F2-1 Supply internal electronics-1
315 mA Slow
F3-2 Supply internal electronics-2
315 mA Slow
F4-2 Fan supply (N)
6,3 Amp. Slow
F5-2 Fan supply (L)
6,3 Amp. Slow
F1-2 Heating
10 Amp. Slow
F2-2 Water valve
1 Amp. Slow
EPROM Version
: 230Vac Version V1.09
FC 500-PC 120 Vac
Power supply voltage
: 100Vac .. 130Vac
Power supply frequency
: 50/60Hz
On/Off switch before FC500-PC
: min. 10A
Power supply cable
: 2,5mm² (14 AWG) flexible or solid wiring stripped 9mm.
Fan-control output
: 42 Vac .. 120Vac (20..50 or 20..60 Hz)
Maximal load fan-control output
: 260VA (Max. 2,2 Amp).
Water valve output
: 120Vac
Chill chaser (heater)
: 120Vac
Internal fuses
: F2-1 Supply internal electronics-1
315 mA Slow
F3-2 Supply internal electronics-2
315 mA Slow
F4-2 Fan supply (N)
6,3 Amp. Slow
F5-2 Fan supply (L)
6,3 Amp. Slow
F1-2 Heating
10 Amp. Slow
F2-2 Water valve
1 Amp. Slow
EPROM Version
: 120Vac Version V1.09
General
Dimensions
: FC500-PC (HxWxD)
250 x 170 x 142 mm
FC400 Display (HxWxD)
102 x 102 x 44 mm
Temperature ranges
: Setpoint
+9/+29
C (+48/+85
F)
Air sensor
-20/+100
C ( -4/+212
F)
Water sensor
-20/+100
C ( -4/+212
F)
Default settings
: See parameter list
Inputs
:Air-sensor 2,2m
(10K NTC)
Water-sensor 2,2m
(10K NTC)
Outside-sensor 2,2m
(10K NTC)
Humidity-sensor e.g. RH95-2
(3-wire RH-sensor)
Contact-input
(Digital input)
Outputs
: Analog output 0-10Vdc
(Rload min. 10Kohm)