background image

 

ALFA(NET) 51 PI 24Vdc -50/+50°C 

Doc.no.: 150301   version 1.1 

 

 

 

 

    

 

Pagina 3 van 8 

10

 

Error messages 

In the display of the ALFA(NET) 51 PI the following error messages can appear: 

 

LO 

- Minimum alarm. 

 

Solution E1: 

 

HI 

- Maximum alarm. 

 

- Check if the sensor is connected correctly. 

 

E1 

- Sensor-1 failure. 

 

- Check sensor (1000

Ω

/25°C). 

 

 

 

 

 

 

- Replace sensor. 

 

 

-L- 

- In case of sensor short-circuit the display alternates between error-code E.. 

 

 

  and -L-, as indication for a short-circuit sensor. 

 

-H- 

- In case of open-circuit sensor the display alternates between error-code E.. 

 

 

  and -H-, as indication for a open-circuit sensor. 

 

Reset Alarm.  When a error-messages appears it can be resetted by pushing the SET key.  

 

 

The function of this key depends on parameter P37. 

 

 

11

 

Technical data 

Type 

ALFA 51  PI 24Vdc of 

ALFANET 51 PI 24Vdc  

Range 

-50/+50°C   

readout per 0,1°C 

Supply 

24 Vdc    

(14…30 Vdc) 

Display 

3-digit 7-segment  

LED display 

Sensor 

SM 811  2-Wire  

PTC 1000

Ω

/25°C 

Relays 

Ry1 = SPST (NO)  

250V/8A cosphi=1 or 250V/5A cosphi=0.4 

Ry2 = SPST (NO)  

250V/8A cosphi=1 or 250V/5A cosphi=0.4 

Ry3 = SPDT (NO/NC) 

250V/8A cosphi=1 or 250V/5A cosphi=0.4 

Relays have one common (C) 

Analogue output 

0-10Vdc PI-output  

Rload = min. 10KOhm  

Communication 

RS-485 Network  

Twisted-pair shielded 

only at ALFANET 

A, B, 0V  (Twist A and B) 

Control 

By four push buttons on the front 

Front 

Polycarbonate 

Dimensions 

90 x 71 x 58 mm  

(H x W x D) 

Panel cut out 

46 x 71 mm  

(H x W) for front mounting 

Accuracy 

+/- 0,5% of the range 

 

 

- Provided with memory protection during power failure. 

 

- Connection with screw terminals. 

 

- Equipped with senor failure detection. 

 

- Special versions are on request available. 

 

Summary of Contents for ALFA(NET) 51 PI

Page 1: ...51 PI is provided with an RS 485 network connection and can be readout or set by an PC with the ALFANET program connected thru an ALFANET PC Interface 2 Installation On the connection diagram of the A...

Page 2: ...the status of the relays Each display segment shows the status of the relay output showing 0 off and 1 on The code 110 means relay 1 and 2 are on and relay 3 is off 7 Viewing the PI output percentage...

Page 3: ...on parameter P37 11 Technical data Type ALFA 51 PI 24Vdc of ALFANET 51 PI 24Vdc Range 50 50 C readout per 0 1 C Supply 24 Vdc 14 30 Vdc Display 3 digit 7 segment LED display Sensor SM 811 2 Wire PTC...

Page 4: ...larm 1 3 1 02 Function Relay 2 same as parm P01 1 3 2 03 Function Relay 3 same as parm P01 1 3 3 04 Function PI output 1 Cool 2 Heat 3 Cool and Heat 1 3 1 05 Offset temperature sensor Calibration 15 0...

Page 5: ...manual reset 0 No 1 Yes 0 40 Start up delay after power failure 0 99 Minutes 0 41 Forced relay function at sensor failure 0 None 1 Cool 2 Heat 0 2 0 60 Heat on delay 0 99 0 61 Heat off delay 0 99 0 62...

Page 6: ...ALFA NET 51 PI 24Vdc 50 50 C Doc no 150301 version 1 1 Pagina 6 van 8 13 Function diagram...

Page 7: ...ALFA NET 51 PI 24Vdc 50 50 C Doc no 150301 version 1 1 Pagina 7 van 8 14 Connections...

Page 8: ...C Doc no 150301 version 1 1 Pagina 8 van 8 15 Dimensions 16 Address VDH Products B V Tel 31 0 50 30 28 900 Productieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands...

Reviews: