background image

 

NON-PROGRAMMABLE

 

DIGITAL THERMOSTAT 

 

 

 

 

 

 

 

 

 

 

 

TST-EGND06413SCS00 / TST-EGND06413SCS01 

TST-EGND06423SCS00 / TST-EGND06423SCS01 

-Cool, Heat and Ventilation 

-Large, Easy To Read Display 

-Blue Backlight 

-Fahrenheit or Centigrade 

-Auto Recovery 

-2-pipe or 4-pipe Selection 

-DA or DB Type Selection 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specification 

Set-Point Range: 5

-35

(41

-95

Operating difference: 

±

 1

 

Switch current rating: 

<

 2A 

Sensing element : NTC   

Display: LCD 

Power supply:   

TST-EGND06413SCS00: AC85V~260V 50Hz/60Hz 

TST-EGND06413SCS01: AC85V~260V 50Hz/60Hz 

TST-EGND06423SCS00: AC24V 

±

10% 50Hz/60Hz 

TST-EGND06423SCS01: AC24V 

±

10% 50Hz/60Hz 

Dimensions: 86 × 86 × 29.5 mm (W

×

H

×

D) 

Housing: ABS Flame Retardant 

Basic Operation 

Power ON/OFF 

 

To turn the thermostat on, press “

”. Mode symbol (

 

or 

), 

“RT”, and room temperature will be displayed

.   

 To turn the thermostat off, press “

” again. There is no any display 

on LCD and no any output. 

Select Mode 

 Cool Setting: Press “M”, until the “

” is displayed, it will be 

confirmed automatically after 6 seconds. 

 Heat Setting: Press “M”, until the “

” is displayed, it will be 

confirmed automatically after 6 seconds. 

 Ventilation Setting: Press “M”, until the “

” is displayed, it will be 

confirmed automatically after 6 seconds. 

Fan Setting 

 Fan speed select: press the fan button to select “

Hi

Med

Low

Auto

”. In mode “

Auto

”, the fan-speed changed 

automatically. Auto LOW-speed When the difference between 

room-temperature and setting-temperature exceed 1

(2

), Auto 

MED-speed When exceed 2

(4

), Auto HI-speed When exceed 3

(6

). 

Setting Temperature 

 To enter the configuration mode: press ”

5

” or ”

6

” buttons , The “

” 

and “SET” will appear on the display. 

 Press”

5

” or ”

6

” to adjust the Cool Temperature. 

  Press  ”M”  button  once.  The  “

”  and  “SET”  will  appear  on  the 

display. 

 Press ”

5

” or ”

6

” to adjust the Heat Temperature. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error Codes 

E1

 — If the thermostat cannot properly read room temperature, and it 

needs to be adjusted, E1 will be displayed. 

Set Thermostat Configuration 

Configuration  options  are  intended  to  be  selected  at  installation  and 

normally  should  not  be  modified  by  the  home  owner.  These  options  are 

not discussed in the Homeowner’s Guide and therefore must be made as 

part  of  the  installation.  A  special  procedure  allows  entry  in  to  the 

configuration mode. The thermostat will automatically exit this if no button 

is pressed for 90seconds.   

An explanation for each of these and how to enter the configuration mode 

follows. 

To enter the configuration mode: 

Turn  off  the  thermostat  hold  the  fan  button  down  for  approximately  15 

seconds. After 15 the second periof, Option”01” will appear in the display. 

OPTION 01–LOW TEMPERATURE PROTECTION (FROST PROTECTION) 

In the low temperature protection mode, When the thermostat is off , and 

the room temperature is lower than 5

, it will be turned on automatically 

and in heating mode; When the room temperature is higher than 7

, it will 

be turned off automatically. 

TO ADJUST: 

Enter configuration mode (if not already there). 

Use “

5

” and “

6

” buttons to display Option 01.The SET icon should be off. 

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 01 setting.   

Use  “

5

”  and  “

6

”  buttons  to  move  between  the  available  Option  01 

choices of 00(disable) or 01(enable). Factory default is 00. 

Press ”M” button again to return to Option 01. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press” 

  “button 

to exit configuration mode. 

OPTION 02 –FAHRENHEIT/CELSIUS SELECTION 

This option selects Fahrenheit or Celsius operation. 

TO ADJUST: 

Enter configuration mode (if not already there). 

Use “

5

” and “

6

” buttons to display Option 02.The SET icon should be off. 

Press ”M”button once. The SET icon will be come on. The display now 

shows Option 02 setting.   

Use  “

5

”  and  “

6

”  buttons  to  move  between  the  available  Option  02 

choices of F (Fahrenheit) or C (Celsius). Factory default is C. 

Press ”M” button again to return to Option 02. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button to 

exit configuration mode. 

OPTION 03

ROOM TEMPERATURE OFFSET 

This option allows calibration (or deliberate miscalibration) of room 

temperature  sensor.  There  are  various  reasons  why  the  home  owners 

want  to  adjust  the  displayed  temperature.  The  selected  number  is  the 

number  of  degrees,  plus  or  minus,  which  will  be  added  to  the  actual 

temperature. The number can range between -5 and +5. Factory default is 

0. This adjusted value will be used as actual temperature for both display 

and control action. For example, if 2 is selected, 72F actual will read 74F. 

If setpoint is 72, the room will control to an actual value of 70 which will be 

displayed  and  acted  upon  as  if  it  were  72.  The  effect  is  that  a  positive 

number  selection  will  make  the  room  temperature  lower  and  vice  versa. 

This  thermostat is factory  calibrated  within  an accuracy of  plus or minus 

1F, so this adjustment will provide the best accuracy when set to 0. 

TO ADJUST: 

Enter configuration mode(if not already there). 

Use “

5

” and “

6

” buttons to display Option 03.The SET icon should be off. 

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 03 setting.   

Use  “

5

”  and  “

6

”  buttons  to  move  between  the  available  Option  01 

choices of -5 t5 in 1 step. Factory default is 0. 

Press ”M ”button again to return to Option 03. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button to 

exit configuration mode. 

OPTION 04 –AUTO RECOVERY 

Auto recovery feature means the thermostat will retain the previous status 

when  power  is  back.  This  option  can  be  used  to  choose  whether  auto 

recovery feature is enabled. 

TO ADJUST:   

Enter configuration mode (if not already there). 

Use “

5

” and “

6

” buttons to display Option 04.The SET icon should be off. 

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 04 setting. 

 

Use  “

5

”  and  “

6

”  buttons  to  move  between  the  available  Option  04 

choices of 00(disable) or 01(enable). Factory default is 01. 

Press ”M” button again to return to Option 04. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button to 

exit configuration mode.

 

OPTION 06 –DA/DB TYPE SELECTION 

This option selects DA type or DB type operation. DA means that when 

temperature reaches the set point, valve will close, fan will keep running

;   

DB  means  that  when  temperature  reaches  the  set  point,  Valve  and  fan 

will close together. 

TO ADJUST:   

Enter configuration mode (if not already there). 

Use  “

5

” and  “

6

”  buttons to display  Option  06.The SET  icon should  be 

off. 

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 06 setting.   

Use “

5

” and “

6

” buttons to move between the available Option 06   

choices of 00 (disable) or 01(enable). Factory default is 01. 

Press ”M” button again to return to Option 06. The SET icon will now be   

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button   

to exit configuration mode. 

OPTION 07 –2-PIPE/4-PIPE SELECTION 

This option selects 2-pipe or 4-pipe operation. 

TO ADJUST: 

Enter configuration mode (if not already there). 

Use  “

5

” and  “

6

”  buttons to display  Option  07.The SET  icon should  be 

off. 

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 07 setting.   

Use “

5

” and “

6

” buttons to move between the available Option 07   

choices of 2 (2-pipe) or 4(4-pipe). Factory default is 2. 

Press ”M” button again to return to Option 07. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button   

to exit configuration mode. 

 

 

 

 

TST-EGND06413SCS00: 

TST-EGND06423SCS00: 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                                  2-pipe 

 

 

 

 

 

 

 

 

 

 

 

4-pipe 

 

Thermostat

 

Fan coil 

L(R) 

Val 

Low 

Med 

Hi 

N(C) 

L(R) 

Val2 

Val1 

Low 

Med 

Hi 

N(C) 

 

Set temperature 

 

Invalid      Fan Button    Down Button    Up Button 

Room temperature 

Cool mode  Heat mode  Ventilation 

Fan indicator 

Mode Button

 

Shows room temperature, 
desired 

temperature,

 and 

other feature information 
as required.

 

On/Off Button 

Wire Diagram 

THERMOSTAT

 

Fan coil 

L(R) 

Val2 

Val1 

Low 

Med 

Hi 

N(C) 

 

L(R) 

Heating Val 

Cooling Val 

Low 

Med 

Hi 

N(C) 

 

Reviews: