* Setting internal parameters.

Next to the adjustment of the set point, internal settings can be made like differential, sensor offset,
set point range and the functions of the thermostat.
Push the 

DOWN

 key for more than 10 seconds, to enter the 'Internal Programming Menu'. In the left

display  the  upper  and  lower  segment  are  blinking.  Over  the 

UP

  and 

DOWN

  keys  the  required

parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing the

UP

 or 

DOWN

 key to change the value of this parameter.

If 20 seconds no key is pushed, the 

ALFA 52-VS

 changes to the normal operation mode. 

* Parameters ALFA 52-VS

Para-
Meter

Description Parameter

Range

Default
value

05
06

Offset temperature sensor 1
Offset temperature sensor 2

-15.0..+15.0

C

-15.0..+15.0

C

0.0
0.0

10
11
12
13

Switching differential 
Switch on delay
Switch off delay
Parameter 11/12 in seconds or minutes

0.1..20.0
0..99
0..99
0 = seconds
1 = minutes

0.5

0
0
0

20
21
22

Minimum adjustable delta-setpoint
Maximum adjustable delta-setpoint
Read-out above -10

C on whole degrees

0.0..+20.0

C

0.0..+20.0

C

0= No
1= Yes

0.0

20.0

0

40

41

42

Relay function alarm relay

Reset alarm relay after recovered alarm

Reset alarm relay after manual reset

0= fail safe alarm
1= control alarm
0= No
1= Yes
0= No
1= Yes

0

0

0

45
46

Control delay after power failure
Relay active at error control sensor

0..99 min.
0= Non 
1= Relay 1
2= Relay 2

0
0

95
96
97
98
99

Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

0..255
00..99
1..52
0..255
0..999

0
0
1
0
0

* Function diagram.