* Setting internal parameters.

Next to the adjustment of the set point, some other internal settings are possible, like differential,
sensor-offset, set point range.
By pushing the 

DOWN

 key more than 10 seconds, you enter the 'internal programming menu'. In

the  left  display  the  upper  and  lower  segment  are  blinking.  With  the 

UP

  and 

DOWN

  keys  the

required  parameter  can  be  selected  (see  table  for  the  parameters).  If  the  required  parameter  is
selected,  the  value  can  be  read-out  by  pushing  the 

SET

  key.  Pushing  the 

UP

  and 

DOWN

  keys

allows you to change the value of this parameter.
If after 20 seconds no key is pushed, the 

ALFA(NET) 13 DP

 changes to it's normal operation mode.

* Parameters ALFA(NET) 13 DP Pt100.

Para-
meter

Description Parameter

Range

Standard
Value

04
10
11

21
22
23
24
25
26
27

28

Offset temperature sensor
Startup delay after power failure
Relay on at sensor failure

Differential maximum alarm
Differential minimum alarm
Time delay maximum alarm
Time delay minimum alarm
Offset setpoint High (Max.)
Offset setpoint Low (Min.)
Relay alarm function

(0=watchdog 1=regulated alarm)

Auto reset alarm after temperature recovering 

(0=hold)

-15.0..+15.0

C

0..99 Minutes
0 = No, 1 = Yes

0.1..15.0

C

0.1..15.0

C

0..99 Minutes
0..99 Minutes
-10.0..+10.0

C

-10.0..+10.0

C

0..1

0 = No, 1 = Yes

0.0

0
0

1.0
1.0

0
0

0.0
0.0

0

0

90
95
96
97
98
99

Network number
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

1..250
0..255
00..99
1..52
0..255
0..999

1

-
-
-
-
-