Operating manual
Document nr. : 022091
Version : V2.3
MC 785-SC
Client : General
Page : 25 of 32
Step
Compressor-1
on/off 1KW
model
Compressor-2
on/off 2KW
model
Compressor-3
on/off 4KW
model
Total
x=on
KW
x=on
KW
x=on
KW
KW
%
1
0
0
0
0
0
2
x
1
0
0
1
14
3
0
x
2
0
2
29
4
x
1
x
2
0
3
43
5
0
0
x
4
4
57
6
x
1
0
x
4
5
71
7
0
x
2
x
4
6
86
8
x
1
x
2
x
4
7
100
Example-3: overview of the control steps with the cooling capacity in percentages (x=active)