18
Step 1: Minus terminal
Connect the Power Minus of all modules in parallel. Please note the Power minus is marked with the
symbol -. For connection of the modules an additional bus bar or a wires with cable lug is needed.
Step 2: Plus terminal
Connect the Power Plus of all modules in parallel. Please note the Power Plus is marked with the
. For connection of the modules an additional bus bar or a wires with cable lug is needed.
Step 3: CAN cables
Connect the CAN cables. Connect always modules next to each other (see below picture).
Step 4: CAN termination resistor
Connect the CAN termination resistor. Please make sure that the system is terminated at both
physical ends of the CAN Bus.
7.3
Configuration of a system
It is necessary under the following conditions:
1. If the modules are connected the very first time.
2. If one or more modules are replaced in an already configured system.
3. If new modules are added to an already configured system.
Connect the batteries as described in chapter 7.1 and 7.2.
Step 1: Turn on the system by pressing the button on any battery for 3s to 5s until the LEDs start
flashing orange. Alternatively, the ON/OFF signal at the M12 connector can be switched to GND.
Either just for max. 500ms (used with an external push button) or continuous (used with an external
switch).
Step 2: Press the button at any battery for at least 5s until the LED at this battery turns red (300ms),
off (300ms), green (300ms) and off (600ms) until the configuration is done (LED green). The LEDs of
Summary of Contents for Easy Blade 24 V