For removal of the module connector loosen the screw and remove the module connector. If the
connector is stuck, use a screwdriver for pulling it out of the recess via the side opening in the
connector.
The modules can be connected in z1 (Easy Blade) and z3 (Easy Block) directions. You can stack the
batteries via the design features on the bottom and on the top of each module. (see below picture).
Please note the stacking features are only for orientation not for fixation. The user is responsible, to
make sure that the module can´t move during operation.
Below table shows the permitted layers in a specific direction:
Direction
Maximal Layers
Comments
Z1
3 layers
To avoid too much weight
Y1
1 layer
To ensure proper ventilation
Z2
5 layers
To avoid too much weight
Y2
1 layer
To ensure proper ventilation
Z3
3 layers
To avoid too much weight
7.2
Electrical connection
It is not allowed to connect the modules in series. Only connect the battery modules in parallel.
Do not mix up 24V and 48V battery modules within a system.