Vedolux 37

•  Boiler installation must be carried out in 

accordance with the Regulations for New 

Buildings [Nybyggnadsreglerna] and the 

Hot Water Instructions [Hetvattenanvisn

-

ingarna].

•  The boiler must be installed indoors in a 

cellar or on the ground floor. The instal

-

lation site must be able to support the 

combined weight of the boiler, the ac

-

cumulator tank and any chimney.

•  The boiler can support up to 250 kg of the 

weight of the chimney.

•  Adjust the base bolts to make the boiler 

level.

•  A temperature limiter must always be 

installed with the boiler.

•  The boiler must be connected to an accu

-

mulator tank, and the installation must include an accumulator control.

•  You must contact the chimney sweep before changing to a different form of 

energy.

•  Contact the municipality to find out about restrictions on the use of solid 

fuels in built-up areas.

•  The fresh air intake of the boiler room must have at least the same cross 

sectional area as the chimney, and it must be designed so it is impossible to 

close it by mistake.

Chimney

The Vedolux 37 has a suction fan minimising the chimney require

-

ments.
If the boiler is connected to the chimney higher up than the previ-

ous boiler, the lower, unused, part must be filled.

Flue pipe

The boiler is supplied with an angled flue pipe – a flue pipe for 

steel pipe is available as an accessory. The flue pipe can be 

turned, and is fixed with four bolts. If the angle is not correct 

initially, the bolts can be inserted in alternative locations. Do not 

forget the washers. See also the diagram on the next page.

Chimney
Height: 

min 3.5 metre

Flue duct:
  Recommended: 

Ø 145 mm 165cm

2

  Min: 

Ø 100 mm 79cm

2

Draught: 

min 10 Pa

F

i

l

l

e

r

Flue gas thermometer

The supplied flue gas thermometer is fitted to the removable 

plate at the front of the flue pipe, in the predrilled and threaded 

hole.

Connection to accumulator system

The boiler must always be connected to an accumulator tank with 

an accumulator control.
The accumulator volume is dimensioned according to the sur-

face area to be heated. Allow for 8 – 10 litres of tank volume per 

square metre of heated surface area.

The schematic diagram below shows the Vedolux 37 with the 

Aqualux and Aqualux UB accumulator tanks plus Accumulator 

Control 3. For more details, refer to the documentation supplied 

with the relevant product. Follow the installation instructions in the 

documentation.
The pipe dimension between the boiler and the tank should be 

28/35 mm for copper pipe or equivalent.

Function of accumulator control

The accumulator control ensures that the boiler reaches a high 

working temperature before it starts charging the accumulator 

tank. It also prevents the return temperature to the boiler falling 

too low, helping to minimise the risk of condensation in the com-

bustion chamber.
The charging pump of the accumulator system is controlled by a 

flue gas thermostat. When the flue gas temperature reaches the 

value set on the thermostat, the pump starts running, circulat-

ing hot water from the top of the boiler, through the accumulator 

control, and back to the return connection on the boiler.

When the boiler temperature reaches around 70°C, some of 

the hot water from the top of the boiler is circulated to the top 

of the accumulator. Cold water is taken from the bottom of the 

accumulator and is circulated to the accumulator control, where 

it is mixed with hot water from the top of the boiler to prevent the 

return temperature to the boiler falling below 72°C. This creates 

pronounced temperature stratification in the tank.

To prevent the accumulator water cooling down unnecessarily, 

the flue gas thermostat stops the charging pump when the flue 

gas temperature falls below the specified value.

A non-return valve in the accumulator control prevents unwanted 

natural circulation when the charging pump is not running.

Shunt valve

The Vedolux 37 does not have a shunt valve to control the tem

-

perature to the heating system. In Värmebaronen systems, the 

valve is fitted to the accumulator tank with water heater, Aqualux 

CU.

VENTED SYSTEM

VENTING

UNVENTED 

SYSTEM

cold water

hot water
riser
return

immersion heater

isolating valve
automatic bleed valve

Installation

Chimney

Location of 

boiler

Flue gas thermometer

Bracket for
cleaning tool

Summary of Contents for Vedolux 37

Page 1: ...ion operation and maintenance Vedolux 37 08 03 ver 3 RVR 0811 From serial no VB THL product no Arkelstorpsv gen 88 291 94 KRISTIANSTAD Tel 044 22 63 20 Fax 044 22 63 58 info varmebaronen se ww varmeba...

Page 2: ...eaning All flue ducts in the boiler are cleaned from the same hatch at the front of the boiler The hatch is hinged and is opened with a single operation The flue ducts are round which means there are...

Page 3: ...nnection fan 17 Electrical connection circulation pump for accumulator charging 18 Flue pipe straight up with socket R25 for support pipe accessory 19 Base frame accessory The manufacturer reserves th...

Page 4: ...urface area The schematic diagram below shows the Vedolux 37 with the Aqualux and Aqualux UB accumulator tanks plus Accumulator Control 3 For more details refer to the documentation supplied with the...

Page 5: ...draining For filling the shunt valve must be fully open Turbulators The five turbulators are installed in the flue gas pipes as shown in the diagram The purpose of the turbulators is to introduce turb...

Page 6: ...9 20 21 22 23 24 26 15b 17b 16b 20 22 21 25 26 27 28 24 Time relay delayed cutoff 25 Overheating protection 26 Indicator showing triggered over heating protection 27 Thermometer displays the boiler te...

Page 7: ...fter the leaves have come out then wait a few weeks before trimming and splitting the wood During these weeks the leaves wilt and draw out the moisture After another few weeks of drying the wood has 2...

Page 8: ...d hatch followed by the bypass damper If the flue gas temperature increases you know that the firewood has ignited When the firewood has burnt and the flue gas temperature has fallen to be low 120 C t...

Page 9: ...less of the heat escapes with the flue gases One way of telling whether it is time for cleaning is to check the flue gas thermostat It is a good idea to clean the boiler if the flue gas temperature is...

Page 10: ...on the height difference between the highest and lowest points in the system the static head Note that the pressure in the system varies with the boiler tem perature do not add water unnecessarily The...

Page 11: ...increased quickly before charging begins Add a control system Ceramic not correctly positioned If the boiler is new check that the ceramic has not moved during transport There is no need to remove the...

Page 12: ...Draught hatch V 37 1 37 00 60 Handle knob 25 mm 2 28 38 00 01 Manometer 0 4 bar 1 27 38 00 03 Thermometer 0 120 C 1 38 00 30 Flue gas thermometer 50 500 C 1 44 00 02 Pipe cleaner 89 mm 2 44 00 05 Pip...

Reviews: