Varmebaronen Vedolux 30 Installation, Operation And Maintenance Manual Download Page 6

6

VÄRMEBARONEN VEDOLUX 30

  The installation must comply with the applicable 

regulations and standards.

The boiler must be installed indoors in a cellar or on the 
ground floor. The installation site 
must be able to support the com-
bined weight of the boiler, the accu-
mulator tank and any chimney.
The boiler can support up to 150 kg 
of the weight of the chimney.
Adjust the base bolts to make the 
boiler level.
A discharge pipe connected to the 
safety valve is to be installed in a 
continuously downward and in a 
frost-free enviroment.

A thermal discharge safety device 

(STW) must always be installed on 

the boiler, cold water  approx. 10

°

C, min 2 Bar.

The boiler must be connected to an accumulator tank, and 
the installation must include an accumulator control, min. re-
turn temp. 60°C
You must contact the chimney sweep before changing to a 
different form of energy.
Contact the municipality to find out about restrictions on the 
use of solid fuels in built-up areas.
The fresh air intake of the boiler room must have at least the 
same cross sectional area as the chimney, and it must be de-
signed so it is impossible to close it by mistake.

Chimney

The Vedolux 30 has a suction fan minimizing the chimney require-
ments.

Flue gas thermometer

Flue pipe

The boiler is supplied with an angled flue 
pipe – a flue pipe running up from the 
steel pipe is available as an accessory.
Fasten the flue pipe to the flange on 
the boiler using the 4 x M8 screws 
supplied, with washers. Remove 
the cleaning hatch first. Two sets 
of holes are provided to cover the 
360° angle of rotation.

Flue gas thermometer

Install the supplied flue gas thermometer in the outlet of the flue 
pipe, see the illustration above.

Connection to accumulator system

The boiler must always be connected to an accumulator tank with 
an accumulator control. 
The accumulator volume is dimensioned according to the surface 
area to be heated. Allow for 8 – 10 litres of tank volume per square 
metre of heated surface area. 
The schematic diagram below shows the Vedolux 30 with the 
Aqualux and Aqualux UB accumulator tanks plus Accumulator 
Control 3. For more details, refer to the documentation supplied 
with the relevant product. Follow the installation instructions in the 
documentation. 
The pipe dimension between the boiler and the tank should be 
28/35 mm for copper pipe or equivalent. 
This diagram illustrates the system principle – the actual system 
will be designed according to the applicable standards and the 
instructions supplied with each component.

Installation

  Minimum distance of 200 mm between rear of boiler 

and wall!

STW
Cold water
(or vice versa)

UNVENTED
SYSTEM

VENTED
SYSTEM

HW

11

46

47a

47b

48

49

50

51

52

53

54 55

56 57

58

59

60

11

48

60

Summary of Contents for Vedolux 30

Page 1: ...Installation operation and maintenance Firewood boiler Vedolux 30 131216 V30 en_mcs rev1...

Page 2: ...at you must or must not do in order to avoid personal injury Tells you what you must or must not do in order to prevent damage or disturbance to the component the burner the process or the surrounding...

Page 3: ...3 V RMEBARONEN VEDOLUX 30 To be completed when the Vedolux 30 is installed Serial number Installation date Installer Tel Other Notes...

Page 4: ...rewood is added Flue cleaning All flue ducts in the boiler are cleaned from the same hatch at the front of the boiler The hatch is hinged and is opened with a single operation The flue ducts are round...

Page 5: ...drop 45 mBar 20 C 1 13 m h 58 mBar 10 C 1 46 m h Weight empty filled with water 290 390 kg kg Volume 100 litre Design pressure 1 5 bar Test pressure 2 15 bar Pressure drop water flow 0 54 l s 10 mbar...

Page 6: ...boiler is supplied with an angled flue pipe a flue pipe running up from the steel pipe is available as an accessory Fasten the flue pipe to the flange on the boiler using the 4 x M8 screws supplied wi...

Page 7: ...il this must be supplemented with a STW STW thermal discharge safety device is used for limiting the temperature by opening a valve normally by circa 97 C and letting cold water enter the cooling coil...

Page 8: ...firewood is burnt out and the flue gas temperature falls below the value set for the thermostat 21 the fan and charging pump stop running If the boiler temperature exceeds 105 C the overheating protec...

Page 9: ...n moisture instead of drying out Ideally the wood should be kept under a roof but in a place where the sun and wind can help dry it The best place for final drying is the boiler room for 2 3 weeks bef...

Page 10: ...ing wood you must open the bypass damper before opening the firewood hatch Only add more firewood when all that is left of the previous load is a layer of embers Constantly topping up with the occasio...

Page 11: ...it is time for cleaning is to check the flue gas ther mostat It is a good idea to clean the boiler if the flue gas tempera ture is approx 25 C higher than the temperature in a clean boiler Open the c...

Page 12: ...hest points in the system the static head If the difference is 5 metres the pressure is 0 5 bar if it is 10 metres the pressure is 1 bar The necessary pressure in the heating system depends on the hei...

Page 13: ...ntrolsystem Ceramicnotcorrectlypositioned Iftheboilerisnew checkthattheceramichasnotmovedduring transport Alsocheckthesealwiththecombustionchamberwalls Highfluegastemperature Tarandsootinthepipes Inco...

Page 14: ...4 03 Grate rear V 30 1 9 71 05 06 Firewood hatch 1 10 71 04 94 Draught hatch V 30 1 37 00 60 Handle knob 25 mm 2 28 38 00 01 Manometer 0 4 bar 1 27 38 00 03 Thermometer 0 120 C 1 38 00 30 Flue gas the...

Page 15: ......

Page 16: ...Varmebaronen UK 11 Back O Hill Stirling FK8 1SH T 01786 849 099 F 01786 849 098 www varmebaronen org info varmebaronen org...

Reviews: