VÄRMEBARONEN VEDOLUX 30
The installation must comply with the applicable
regulations and standards.
The boiler must be installed indoors in a cellar or on the
ground floor. The installation site
must be able to support the com-
bined weight of the boiler, the accu-
mulator tank and any chimney.
The boiler can support up to 150 kg
of the weight of the chimney.
Adjust the base bolts to make the
boiler level.
A discharge pipe connected to the
safety valve is to be installed in a
continuously downward and in a
frost-free enviroment.
A thermal discharge safety device
(STW) must always be installed on
the boiler, cold water approx. 10
°
C, min 2 Bar.
The boiler must be connected to an accumulator tank, and
the installation must include an accumulator control, min. re-
turn temp. 60°C
You must contact the chimney sweep before changing to a
different form of energy.
Contact the municipality to find out about restrictions on the
use of solid fuels in built-up areas.
The fresh air intake of the boiler room must have at least the
same cross sectional area as the chimney, and it must be de-
signed so it is impossible to close it by mistake.
Chimney
The Vedolux 30 has a suction fan minimizing the chimney require-
ments.
Flue gas thermometer
Flue pipe
The boiler is supplied with an angled flue
pipe – a flue pipe running up from the
steel pipe is available as an accessory.
Fasten the flue pipe to the flange on
the boiler using the 4 x M8 screws
supplied, with washers. Remove
the cleaning hatch first. Two sets
of holes are provided to cover the
360° angle of rotation.
Flue gas thermometer
Install the supplied flue gas thermometer in the outlet of the flue
pipe, see the illustration above.
Connection to accumulator system
The boiler must always be connected to an accumulator tank with
an accumulator control.
The accumulator volume is dimensioned according to the surface
area to be heated. Allow for 8 – 10 litres of tank volume per square
metre of heated surface area.
The schematic diagram below shows the Vedolux 30 with the
Aqualux and Aqualux UB accumulator tanks plus Accumulator
Control 3. For more details, refer to the documentation supplied
with the relevant product. Follow the installation instructions in the
documentation.
The pipe dimension between the boiler and the tank should be
28/35 mm for copper pipe or equivalent.
This diagram illustrates the system principle – the actual system
will be designed according to the applicable standards and the
instructions supplied with each component.
Installation
Minimum distance of 200 mm between rear of boiler
and wall!
STW
Cold water
(or vice versa)
UNVENTED
SYSTEM
VENTED
SYSTEM
HW
11
46
47a
47b
48
49
50
51
52
53
54 55
56 57
58
59
60
11
48