Manual and Data Sheet NSE Version 1.0 

 

Variotech – Emergency power supply unit NSE Version 1.0

 

Date: 10.01.14, Page 5 of 7 

 

Environmental conditions: 

The NSE is designed so that it pollutes the environment as little as possible. It emits no pollutants and 
does not contain environmentally harmful substances and consumes very little power. 

Conditions of use: 

The NSE power supply must be used only under the following conditions: 

a.)  The brake element of the protective device must be type-approved. 
b.)  Appropriate self-monitoring of the correct functioning of the braking device must be provided.  

The power supply unit NSE cannot execute this function. 

Assembly / Mounting:  

Installation of security control should preferably be close to the elevator control. If more space is 
available in the control box, a free DIN rail with of about 10cm length is required. If there is no space 
available, it is possible to mount the unit nearby to the control box.  
In that case the NSE can be delivered in a special industrial plastic housing. 
The unit must be installed in a housing with a protection factor of at least IP4x. 

Connections and terminals description: 

Terminal 1 (+V), 2 (-V):

 Connection of a suitable external power supply with an input voltage of 230V 

and an adjustable output voltage from 12VDC + / -20% min 3A. The output voltage must be set to 13.6 
volts before commissioning (suitable power supply would be Meanwell MDR-40-12). 

Terminal 3:

 Connection for the potential-free output contact (relay) "power ok" of the power supply. 

Terminals 4, 5:

  Connection for a safety relay contact of the A3 safety control, which opens in case of 

an A3 error. This input is used to turn off the supply voltage of the A3 brake element if an A3 error 
occurs. 

Terminals 6(-V), 7 (+V):

  Connection of the power supply 24V DC 0,3A of the A3 safety control. 

Terminal 8:

 Reset button output for connection to the reset button input of A3 safety control.  

Terminal 9:

 Output "feedback of the A3 brake element" to connect to the A3-safety control.  

This output indicates the function of the A3 brake element. The switch position is dependent on the 
switch on the A3 brake element. 

Terminals 10 (+V), 11 (-V):

 Connection of an external 12V battery. The battery can have a capacity 

ranging from 1.2 Ah to 7.5 Ah 

Terminals 12, 13: 

 Output (potential-free relay contact, normally closed) for reporting a battery failure.  

Terminals 14, 15:

 Connection for an external switch for the initiation of the emergency rescue and as 

well as for the reset of the A3 safety control. 

Terminals 16, 17:

 Connection for an external LED which indicates if the coil is active. 

Terminals 18 (-V), 19 (+V):

  

Output voltage 24VDC for the A3 brake element. 

Terminals 20, 21: 

 Connection for the switch (feedback control) on the A3 brake element. 

Signal transmitter:  

The power supply NSE has a built-in electric signal transmitter (beeper / buzzer) which generates an 
acoustic signal to indicate an error and easier fault location in case of error. 

Summary of Contents for NSE

Page 1: ...and liability management 3 Intended use 3 Commercial data 3 Product details 3 Function 3 Product description 4 Layout and connections 4 Technical Details 4 Environmental conditions 5 Conditions of us...

Page 2: ...er a 24V power supply and battery backup NSE The power supply NSE requires an input voltage of 13 6 V DC galvanically isolated from the mains power supply The power supply NSE generates the charging v...

Page 3: ...in of other systems or particular in industrial plants The safety control ENA3 may only be used for the case defined in EN81 Annex 3 to prevent of an unintendend movement of the car from a standstill...

Page 4: ...oltage of 24VDC from the 12V battery This only requires a single 12V battery Reverse polarity protection and automatic reset fuse at the battery clamp Automatic lowering of the supply voltage of the A...

Page 5: ...itable power supply would be Meanwell MDR 40 12 Terminal 3 Connection for the potential free output contact relay power ok of the power supply Terminals 4 5 Connection for a safety relay contact of th...

Page 6: ...continuity tester If the battery is OK the two terminals have the same potential Check the correct connection of the emergency rescue button to terminals 14 and 15 with a continuity tester Terminal 1...

Page 7: ...talled in a control box On request the unit can also be supplied already mounted in an industrial plastic housing IP65 The complete system ENA3 NSE BOX consists of a pre wired and pre assembled ENA3 c...

Reviews: