PRIMARY FUNCTIONS
MAIN SET POINT
The main set point establishes the target
temperature in the building. This value is used
as the reference point for other settings. The
main set point temperature is adjusted in 0.5
degree increments from a minimum setting of
13.5°F (-9.5°C) to a maximum setting of 105.0°
F (41.0°C).
Adjusting the main set point temperature:
•
rotate the Selector dial to position (1),
•
rotate the Adjuster dial counterclockwise to
decrease the temperature setting, and
clockwise to increase it.
The main set point temperature is displayed on
the MST-5.
Note: The ramping feature (primary
function 9) must be (OFF) to adjust the
main set point.
CHAPTER 3 - USER’S GUIDE
www.monitrol.com