Page 49
DESCRIPTION
VALUE
INPUT POWER
−
12 AMP
−
115/230 -20%, +10% VAC
−
50 / 60 Hz
STAGE 1 (variable speed)
−
6 AMP; inductive 115V / 230V
−
10 AMP; max (fuse 10A)
STAGE 2 (variable speed)
−
6 AMP; inductive 115V / 230V
−
10 AMP; max (fuse 10A)
STAGE 3 (dry relay
contact)
Not Fused
−
10 AMP ; 115V/230V
−
1/2 HP @ 115V
−
1 HP @ 230V
−
Min. Rating 10mA at 115V*
−
20mA at 230V*
STAGE 4 (dry relay
contact)
Not Fused
−
10 AMP ; 115V/230V
−
1/2 HP @ 115V
−
1 HP @ 230V
−
Min. Rating 10mA at 115V*
−
20mA at 230V*
STAGE 5 (dry relay
contact)
Not Fused
−
10 AMP ; 115V/230V
−
1/2 HP @ 115V
−
1 HP @ 230V
−
Min. Rating 10mA at 115V*
−
20mA at 230V*
ALARM (dry relay
contact)
−
2 AMP; 30V AC/DC
SPECIFICATIONS
APPENDIX
* Relay will not function properly if load is smaller than the
min. value.