ECS 5M
HIGH TEMPERATURE ALARM
This function establishes the temperature
difference
above the main set point that the
room can reach before a high temperature
alarm is signalled. When a high temperature
alarm occurs an alarm contact is activated and
the alarm LED lights on the ECS.
The high temperature alarm is adjusted in 0.5
degree increments from a minimum setting of
0°F (0°C) to a maximum setting of 32.0°F
(18.0°C)
Adjusting the high temperature alarm:
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
•
rotate the Selector dial to position (11),
•
rotate the Adjustor dial counterclockwise to
decrease the setting, clockwise to increase
it.
The high temperature alarm setting is
displayed on the ECS.