![Varian TV 301 Navigator Instruction Manual Download Page 84](http://html.mh-extra.com/html/varian/tv-301-navigator/tv-301-navigator_instruction-manual_854757084.webp)
TECHNICAL INFORMATION
Command: STOP
Source: PC
Destination: Controller
02 80 30 30 30 31 30 03 42 32
STX ADDR
WINDOW
WR OFF ETX
CRC
Source: Controller
Destination: PC
02 80 06 03 38 35
STX ADDR ACK ETX
CRC
Command: SOFT-START (ON)
Source: PC
Destination: Controller
02 80 31 30 30 31 31 03 42 32
STX ADDR
WINDOW
WR ON ETX
CRC
Source: Controller
Destination: PC
02 80 06 03 38 35
STX ADDR ACK ETX
CRC
Command: SOFT-START (OFF)
Source: PC
Destination: Controller
02 80 31 30 30 31 30 03 42 33
STX ADDR
WINDOW
WR OFF ETX
CRC
Source: Controller
Destination: PC
02 80 06 03 38 35
STX ADDR ACK ETX
CRC
Window Meanings
N. Read/
Write
Data
Type
Description Admitted
Values
000 R/W
L Start/Stop
(in remote mode
the window is a
read only)
Start = 1
Stop = 0
008 R/W
L Remote
(default) or Serial
configuration
Remote = 1
Serial = 0
(default = 1)
100 R/W
L Soft
Start
(write only in
Stop condition)
YES = 1
NO = 0
101
R/W
N
Set Point type
0 = Frequency
1 = Current
2 = Time
(default = 0)
102
R/W
N
Set Point
threshold
(expressed in Hz,
mA or s)
(default = 867)
103
R/W
N
Set Point delay:
time between the
pump start and
the set point
check (seconds)
0 to 99999
(default = 0)
104
R/W
L
Set Point signal
activation type:
the signal can be
"high level active"
or "low level ac-
tive"
0 = high level ac-
tive
1 = low level ac-
tive
(default = 0)
105 R/W N Set
point
hysteresis
(in % of threshold)
0 to 100
(default = 2)
106
R/W
L
Water cooling
0 = NO
1 = YES
107 R/W
L Active
Stop
(write only in
stop)
0 = NO
1 = YES
108
R/W
N
Baud rate
600 = 0
1200 = 1
2400 = 2
4800 = 3
9600 = 4
(default = 4)
109
W
L
Pump life/ cycle
time/ cycle num-
ber reset
To reset write ‘1’
110
R/W
L
Interlock type
(default = 1)
Impulse = 0
Continuous = 1
111 R/W
L Analog
output
type: output volt-
age signal pro-
portional to
frequency or
power
0 = frequency
1 = power
(default = 0)
120 R/W N Rotational
fre-
quency setting
(Hz)
150 to 963
(default = 963)
79