TECHNICAL INFORMATION
32
87-900-120-01 (A)
Win.
no.
Read/
Write
Data
Type
Win.
Name
Description
Admitted val.
100
R/W
N
Local/Remote/
Analog Selection
Selezione Local/Serial/Analog.:
0 Serial
1 Local
2 Analog
0-2
120
R/W
L
Backlight
Backlight On/Off
0-1
130
R/W
N
Language
Language selection:
0 Italiano
1 English
2 Francais
3 Deutsch
140
R/W
N
Measurament Unit
Unit of measurement selection:
0 PPM
1 mbar1/s
2 cm3/s
3 cm3/min
4 TorrL/s
5 PaL/s
6 Pam3/s
7 Kg/h
8 g/y(R12)
9 g/y(R314)
10 SCF/Y
0-10
150
R/W
L
Zero Function
Auto zero / Fixed zero selection
0-1
160
R/W
N
Sensitivity Selection Sensitivity selection:
0 LS
1 HS
2 VHS
0-2
170
R/W
L
Probe Function
Sampling enabling
0-1
180
R/W
L
Audio Signal
Audio signal enabling
0-1
190
R/W
L
CleanUp Function
Clean-up enabling
0-1
270
R/W
N
Measurament
Helium concentration measurement (PPM)
0-900'000
280
R/W
L
Set Point 1 Enable
Enabling Set Point 1
0-1
290
R/W
L
Set Point 2 Enable
Enabling Set Point 2
0-1
300
R/W
L
Set Point 3 Enable
Enabling Set Point 3
0-1
310
R/W
L
Set Point 4 Enable
Enabling Set Point 4
0-1
315
R/W
L
Safety Set Point
Enable
Enabling Safety Set Point
0-1
319
R/W
A
Pcb P/N
Part Number of Pcb
-
320
R/W
A
PHD P/N
Part Number of PHD
-
322
R/W
A
PHD S/N
Serial Number of PHD
-
323
R/W
A
Pcb S/N
Serial Number of Pcb
-
324
R/W
A
PHD Modific. Level
upgrade level of the PHD
-
325
R/W
A
Pcb Modific. Level
Upgrade level of the Pcb
-
330
R/W
L
Valve Enable
Backflow valve enabling
0-1
340
R/W
L
Heater enable
Heater OFF enabling
0-1
350
R/W
N
Set Point 1 Value
Set point 1 threshold (PPM)
0-900'000
360
R/W
N
Set Point 2 Value
Set point 2 threshold (PPM)
0-900'000
370
R/W
N
Set Point 3 Value
Set point 3 threshold (PPM)
0-900'000
380
R/W
N
Set Point 4 Value
Set point 4 threshold (PPM)
0-900'000
390
R/W
N
Safety Set Point
Value
Set point Safety threshold (PPM)
0-900'000