Vapac, Virtuoso VE Humidifier, Installation Manual, EN 2024-01, D301474 Iss 0 Page No 43 of 80
C
ModScan
Register
Variable
Description
R/W Saved
Default
40021
20
MaxOperatingCurrent
Maximum operating current for this Model
from lookup table
RO
40022
21
PCSCC
Power consumption since cylinder changed
(not used)
RO
yes
40023
22
HumiditySetpoint
Required Humidity(0-100%) when
DemandInputType=1
RW
yes
50
40024
23
HumidityValue
Current Humidity value from sensor (0-
100%)
RO
40025
24
HumidityControlDemand
Output
Demand used when the external input is
active
RW
yes
40026
25
"ServiceAlarmEncode
0 - FAULT1_FEED_VALVE
1 - FAULT1_LOW_OUTPUT1
2 - FAULT1_LOW_OUTPUT2
3 - FAULT1_DRAIN
4 - ALARM1_OVERCURRENT
5 - ALARM1_HIGH_
OVERCURRENT
6
7
8 - FAULT2_FEED_VALVE
9 - FAULT2_LOW_OUTPUT1
10 - FAULT2_LOW_
OUTPUT2
11 - FAULT2_DRAIN
12 - ALARM2_
OVERCURRENT
13 - ALARM2_HIGH_
OVERCURRENT
"Bitmap code of Faults/Alarms
1 - Cylinder 1 Feeding for longer than R65
MaxFeedTime
2 - Cylinder 1 Low output fault 1 see
manual
4 - Cylinder 1 Low output fault 2 see
manual
8 - Cylinder 1 Draining for longer than R51
TotalDrainTime
16 - Cylinder 1 Overcurrent fault > 112% of
Max Operating Current
32 - Cylinder 1 High Overcurrent fault >
115% of Max Operating Current
Unused
Unused
256 - Cylinder 2 Feeding for longer than
R65 MaxFeedTime
512 - Cylinder 2 Low output fault 1 see
manual
1024 - Cylinder 2 Low output fault 2 see
manual
2048 - Cylinder 2 Draining for longer than
R51 TotalDrainTime
4096 - Cylinder 2 Overcurrent fault > 112%
of Max Operating Current
8192 - Cylinder 2 High Overcurrent fault >
115% of Max Operating Current
RO
yes
40027
26
MaxPowerRating
Maximum power rating of unit in (kW) from
lookup table
RO
40028
27
SteamOutput
Steam ouput of unit in Kg/Hr from lookup
table
RO
40029
28
CurrentSteamDemand
Current Steam ouput Demand (Kg/Hr) based
on requested demand (0-100%)
RO
40030
29
ExternalDemand
"When R17 DemandInputType=0 this shows
demand as per 0-10v input
When R17 DemandInputType=2 this is the
required demand"
RO
40031
30
ServiceHoursInterval
The interval in hours before a service is
required
RW
yes
40032
31
TotalPowerConsumption
Total power used since unit
RO
yes
40033
32
SerialNumber
16 bit serial number if required (0-65535)
RW
yes
40034
33
SoftwareVersion
Software version number from compiled
source eg V1.06 = 106
RO
40035
34
TemperatureInput
Temperature in °C from connected 10K3A1
Thermistor, 200 = 20°C
RO
40036
35
AlarmReset
1=Reset all Fault/Alarm codes R25
ServiceAlarmEncode
RW