Vapac, Virtuoso VE Humidifier, Installation Manual, EN 2024-01, D301474 Iss 0 Page No 13 of 80
I
Do not use the handles on the side
of the humidifier cabinet to lift the
unit.
Ensure that the humidifier is
installed in a level plane.
The humidifier is designed for
wall mounting using the bracket
provided with the appliance.
Do not add additional weight to
the mounted humidifier.
The humidifier is delivered in a packaging
carton on a cardboard base and wooden pallet
as discussed in the "Unpacking / Preparation"
section earlier; leave the unit on the base and
pallet until you are ready to hang it. If the
bottom of the unit is not protected or supported
prior to installation, damage can occur.
To mount the humidifier:-
1. Position the supplied bracket on the wall,
using the printed template supplied with the
unit.
2. Drill suitably sized wall bolts into the slotted
holes of the bracket to secure the bracket
to the wall (two for single cylinder units and
three for double cylinder units).
3. Remove the front panel from the humidifier.
4. Secure the humidifier to the bracket by
sliding the open slots on the back of the unit
onto the tab inserts located on the bracket.
5. From inside the humidifier, verify that the
holes in the unit back wall are aligned with
those in the tabs on the bracket.
6. From inside the humidifier, use suitably
sized screws via the holes in the tabs on the
bracket in order to secure the humidifier to
the bracket.
7. For extra rigidity, the unit can be screwed
to the wall via screw hole(s) towards the
bottom of the unit (one for Case A units and
two for Case B and C units).
8. Slide front panel onto unit and close locks.
Please refer to the separate installation
instructions for details of installing and
maintaining the Room Distribution Unit RDU.
Fig 2a - Installation template
Fig 2b - Bracket mounted on wall
Fig 2c - Lifting the unit, front panel removed
Casing outlines
Mounting tabs
Bracket fixing
screws
Mounting
hole
locations