Vapac, Virtuoso VE Humidifier, Installation Manual, EN 2024-01, D301474 Iss 0 Page No 35 of 80
I
Cylinder electric demand loads
Model
VE05-1P
Cylinder
1
1
Nominal Output
kg/hr
5.00
5.00
Nominal Output
lb/hr
11.00
11.00
Voltage
V
200
230
Power input rating
kW
3.73
3.71
Electrical Supply
Ph's
Ph+N or 2Ph
Ph+N or 2Ph
No. of electrodes
2
2
Full load Current
A
22.50
19.50
Maximum overcurrent A
25.9
22.45
Fuse Rating/phase
A
40
32
Supply cable terminals mm
2
10
10
Wiring diagram
D301585
Cabinet size
A
Model
VE09-1P
Cylinder
1
1
Nominal Output
kg/hr
9.00
9.00
Nominal Output
lb/hr
19.80
19.80
Voltage
V
200
230
Power input rating
kW
6.71
6.76
Electrical Supply
Ph's
Ph+N or 2Ph
Ph+N or 2Ph
No. of electrodes
2
2
Full load Current
A
40.50
35.50
Maximum overcurrent A
48.60
41.00
Fuse Rating/phase
A
63
63
Supply cable terminals mm
2
16
16
Wiring diagram
D301585
Cabinet size
A
Model
VE09-3P
Cylinder
1
1
1
1
Nominal Output
kg/hr
9.00
9.00
9.00
9.00
Nominal Output
lb/hr
19.80
19.80
19.80
19.80
Voltage
V
380
400
415
440
Power input rating
kW
6.81
6.89
6.85
6.94
Electrical Supply
Ph's
3Ph
3Ph
3Ph
3Ph
No. of electrodes
3
3
3
3
Full load Current
A
12.50
12.00
11.50
11.00
Maximum overcurrent A
14.38
13.80
13.23
12.85
Fuse Rating/phase
A
20
20
20
20
Supply cable terminals mm
2
10
10
10
10
Wiring diagram
D301586
Cabinet size
A