background image

 

 

20

4.0 Trouble-shooting 

Check 

List 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Use manual drain option to check pump operation 

 
Check/Cause/Remedy 

Check main power is connected and switched on. 

-

 

Check power supply fuses.

 

Preliminary 
 

Symptom 

Power-On Neon – Off 
Symbol-LED – Off 
Display - Blank

 

Power-On Neon – On 
Symbol-LED – On 
Display - Blank

 

Check if security circuit is open circuit 

-

 

Check 24V 6.3A fuse mounted at top of Microvap controller PCB 1150630

 

Automatic STOP – Feed Fault indicated on the Display. 

Possibilities 

Water is not connected 
Water connected but not 
reaching cylinder. 
Water in cylinder and 
overflowing

.

 

Checks

-

 

Check water stop valve is open 

-

 

Check internal Vapac hose connections for a leak. 

 

-

 

Check float switch operation

 

 

Unit On-Line but inadequate or no steam production

Possibilities 

Contactor not made 
MCB’s tripped 
SSR’s not switching

 

Checks

-

 

Contactor coil, Float switches, Control PCB. 

-

 

Cylinder Inspection, inspect elements, and float switch operation. 

-

 

SSR Check as described below,

 

Important 

 
 
Equipment needed 
 
 
Procedure 
 
 
 
 
 
 
 
 
 
 
 
 
 
SSR Replacement

 

Automatic Stop – Drain Fault indicated on the display. 

Specialised check of the Solid State Relay 

 

The following check should be carried out by a competent electrician 

-

 

An AC Voltmeter, multi-meter set to full AC line voltage or suitable voltage test 
instrument. 

 

-

 

Remove access panels from both the steam cylinder and electrical compartments 

-

 

Ensure that the humidifier has an operational level of water in the cylinder. Switch 
unit on and check that the display indicates “Vapac on line”. 

-

 

Apply the voltmeter, set to the ful line Voltage, across the output terminals of the 
SSR being tested (i.e. the two terminals carrying the cabling to the elements).

 

 
Correct Voltmeter Response – oscillating between full and near zero Voltage. 
 

If Voltmeter reads a constant near zero Volts, Check: 
a)  That the unit is not feeding water – if it is, wait until the feed valve closes and then 

re-check. (reason the SSR will hold closed while the feed valve is open). 

b)  That the control PCB is giving the correct pulsed D.C. signal (approx 5V D.C.) to the 

SSR control input terminals. 

 
A faulty SSR should be replaced

 with an SSR of the same (or higher) Voltage and 

amperage rating. Disconnect the unit from the electrical supply. Disconnect the 
SSR and undo the mounting screws. The SSR is bedded in thermal compound 
to assist heat transfer – it is important that this is cleaned off, and a layer fresh 
compound placed under the replacement SSR. When it is secured in position. 
Reconnect the SSR, reconnect the electrical supply and check the SSR 
function as above before replacing the access panels. 
 

Note: Use proprietary thread locking compound on the line voltage 

Possibilities 

Drain pump function impaired 
 
 
Float switch failure 
Cylinder O/Let Blocked 

 

Checks

-

 

If pump will not function, empty cylinder by disconnecting at the tundish fill-cup the 
water supply hose to the cylinder and draining the water into a bucket. Remove, 
dismantle and clean pump. 

-

 

Check float switch operation

 

-

 

Check & unblock 

 

Summary of Contents for LEC05

Page 1: ...the requirements of the RoHS Directive 2002 95 EEC This product will meet the requirements of the Low Voltage Safety Directive 2006 95 EEC and the EMC Directive 2004 108 EEC when installed in accorda...

Page 2: ...l Control 12 1 6 3 Control Signal Selection 12 1 6 4 On Off Control 12 1 6 5 Sensing Head 13 1 6 6 Security Circuit E P O Shutdown 13 1 6 7 Load Shed Option 13 1 6 8 Master Slave System 14 2 0 Start U...

Page 3: ...the terminals and contactor are tight Check that the transformer primary winding connection is correct for the supply voltage at Vapac terminals A1 A2 The Vapac transformer must not be used to power o...

Page 4: ...the unit in position Don ts Don t mount the unit close to sources of strong electro magnetic emissions e g variable speed lift motor drives kVa transformers etc Don t mount the unit in an unventilate...

Page 5: ...late 120 X 120 Gland Plate 120 X 120 Left Top View Showing Steam O let position Below Rear View showing wall mounting points Left Bottom View Showing F Feed connection BSP male connection for flexible...

Page 6: ...nit of 300mm Do use the full height available between the unit and steam pipe to provide maximum slope min 12 20 for condensate to drain back to the steam cylinder or down to a condensate separator Al...

Page 7: ...and to effect a seal If water seepage occurs undo the nut to wipe the washer clean and re seat it 1 3 2 Drain connection General Do s Do ensure metal drain and supply water pipework is grounded electr...

Page 8: ...sition marked with the supply Voltage that is to be connected between VAPANET power terminals A1 and A2 The transformer primary circuit terminal positions are clearly marked 200V 230V 380 415 440V If...

Page 9: ...547 Normally open when unit is in standby or fault not running If the unit is part of a master slave system or network the run fault outputs can be selected via keypad display as either network system...

Page 10: ...used to ensure cables are held securely at the entry position All Vapac cabinets are equipped with a removable gland plate The installing electrician should remove this and take it to a work bench to...

Page 11: ...h 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph No of electrodes 3 3 3 3 3 3 6 6 3 3 3 3 Full load Current per cylinder A 46 5 40 5 24 5 23 5 22 5 21 5 78 68 41 39 37 5 35 5 Maximum overcurrent per cylinder A 53 475 46 575...

Page 12: ...by either a potentiometric signal a lonworks network signal or by one of 6 standard proprietary DC analogue signals Input signal Potentiometric control 0 5V 0 10V 0 20V Actually 0 18V not phase cut 2...

Page 13: ...10 will prevent any unit operation including frost protection 1 6 7 Load Shed Option This can only be evoked via a display either hard wired or hand held When this option is selected making the conne...

Page 14: ...le in each unit of the system including the master xxxxxx xxxxxx xxxxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxx Esc Vapac J2 Vapac part no 1150631 CR1 Net J1 Vapac PART...

Page 15: ...procedure by selecting the preferred language Attaching the control PCB to the Display nominating the type quality of the supply water nominating the control signal or Vapac sensor when being used Wh...

Page 16: ...ose clip 1 and disconnect the steam hose 4 from the top of the cylinder 6 Using a twisting movement lift the cylinder clear of its seating in the feed drain manifold and carefully remove the used cyli...

Page 17: ...ollows Turn off the water supply to the Unit Undo the nylon nut connecting the flexible connection to the valve inlet The strainer can be removed using long nosed pliers to grip the centre flange prov...

Page 18: ...User LED 2 Description OFF OFF Cylinder 1 and Cylinder 2 in shutdown Or Cylinder 1 in standby and Cylinder 2 in shutdown OFF RED Flashing 1 second period Cylinder 1 and Cylinder 2 in standby Green Am...

Page 19: ...0 50 Timed Drain down Used to drain all the water from the cylinder if the unit remains on standby for longer than a preset but adjustable time period For information on setting these options please s...

Page 20: ...operational level of water in the cylinder Switch unit on and check that the display indicates Vapac on line Apply the voltmeter set to the ful line Voltage across the output terminals of the SSR bein...

Page 21: ...A3 A1 2A Net CR1 CR4 v 0v 2 3 8 9 6 4 5 7 CR6 9v AC Fused Supply Part Number 1150631 1 Blue 1 Brown 2 Blue 2 Brown TO SHEET 3 of 3 SEE NOTE 1 BLUE RED 70 VA Auto wind TAPPING IS A 230 VOLT Red 9v AC...

Page 22: ...dc feed DO 6 DI 6 CYL 2 SSR LEC 9v dc feed DO 5 DI 5 CYL 1 SSR AI 1 V or mA INPUT Demand POT 0v dc Demand POT 5v dc AI 2 CYL 1 CURRENT INPUT AI 1 Ref AI 2 Ref Black Red Black Red White Violet Red Blac...

Page 23: ...hite Pink Pink Violet Pink Pink Pink Violet Pink Pink ANALOGUE INPUT 8 0v COM AI 8 ANALOGUE INPUT 7 0v COM AI 7 ANALOGUE INPUT 6 0v COM AI 6 0v COM AI 5 ANALOGUE INPUT 5 Bond Earth 0V Control Fuse Vio...

Page 24: ...Yellow 26 Blue LE05P and LE09P A1 Ph 1 A2 Ph 2 or N Three Electrode E1 E2 E3 cylinder for SINGLE CYLINDER UNIT LE18 LE30 high voltage TWIN CYLINDER UNIT LE60 High voltage cylinder 1 CONNECTED TO A3 FO...

Page 25: ...oltage and LE60P low voltage SUPPLY DETAILS PLEASE REFER TO FOR ELECTRICAL LOADS AND POWER THE VAPENET LE OPERATION AND MAINTENANCE MANUAL latest Edition CONNECTED TO N FOR 380 440 V 3 PHASE SUPPLY CO...

Page 26: ...LY DETAILS PLEASE REFER TO FOR ELECTRICAL LOADS AND POWER THE VAPENET LEC OPERATION AND MAINTENANCE MANUAL latest Edition Neutral Earth Supply A 3 Phase LOW VOLTAGE AND LEC45 CYLINDER 2 VAPAC SIX ELEC...

Page 27: ...0 LV LEC45 CABLE SIZE in mm2 TRI RATED CABLES SUPPLY DETAILS PLEASE REFER TO FOR ELECTRICAL LOADS AND POWER THE VAPENET LEC OPERATION AND MAINTENANCE MANUAL latest Edition Neutral Earth Supply A 3 Pha...

Page 28: ...e constricted leading to excessive pressure in the steam lines N B Standard steam distribution pipes are manufactured such that any condensate is drained back towards the Vapac steam cylinder Reverse...

Page 29: ...ates that a reverse slope steam pipe is required This is fitted with a drain point to allow condensate to be taken away to a convenient drain Figure 2 shows recommendations on how to space one or more...

Page 30: ...ndensate drain connection 3 Care should be taken to support steam hose sufficiently such that no kinks are formed which would flood with condensate causing the bore of the tube to become constricted l...

Page 31: ...Made in England by Vapac Humidity Control Ltd June 2004 Vapac Humidty Control Ltd reserve the right to change the design or specification of the equipment described in this manual without prior notic...

Reviews: