background image

 

 

16

1

2

3

Full Pin

ONLY BE TAKEN ONCE THE CAUSE OF THE PROBLEM 
HAS BEEN ASCERTAINED AND RECTIFIED.

 

 
2.1

 

Service Advice

 

 

The water hardness and the humidity demand at site will 
determine the effective life of a steam cylinder. Units located 
in areas with naturally soft waters will experience the longer 
cylinder life, possibly upwards of 12 months in calendar 
terms. With hard waters, a more frequent cylinder exchange 
must be expected and cylinder exchange 2 or 3 times a year 
can be the average situation. The normal scaling up of the 
Vapac steam cylinder is outside the Vapac warranty. 
 

2.1.1 

Procedure for cylinder Exchange. 

 

1. 

With the power connected to the unit, manually drain 
the unit, by depressing (and holding) the Run/Off/Drain 
Switch to the lower momentary drain position.

 

 

2. 

Disconnect the Vapac from the incoming electrical 
supply by means of the external isolator (disconnect 
switch). This should be “locked off” to prevent 
accidental operation.

 

 

3. 

Unlock the access panel, and swing open to gain 
access to the steam cylinder.

 

 

4. 

Carefully ease off (lever) the electrode caps (1& 2).  If 
the cylinder is to be replaced, care should be taken not 
to twist the electrode caps while removing the black 
power caps.  As the electrodes can rotate in the 
cylinder bosses (if the plastic cylinder is hot) and lead to 
unbalanced electrical loads.

 

 

5. 

 Loosen the hose clip (1) and disconnect the steam 
hose (4) from the top of the cylinder.

 

 

6. 

Using a twisting movement, lift the cylinder clear of its 
seating in the feed/drain manifold and carefully remove 
the used cylinder from the unit.

 

 

7. 

Inspect the feed/drain manifold to ensure to ensure this 
is clear of sediment.

 

 

8. 

The drain pump can be removed for inspection and 
cleaning, by following the instructions below.

 

 

9. 

With the pump back in position, insert the cylinder into 
the feed/drain manifold, pushing it down firmly to 
ensure it is seated correctly.

 

 

10. 

Reconnect the steam hose.

 

 

11. 

Replace the electrode caps – ensure that the are 
replaced in the same sequence as when removed. With 
the cylinder full pin towards the front of the unit, 
electrode number 1 will be to the left of the white 
cylinder full electrode. Electrodes 2, 3, 4 etc will be 
sequentially connected clockwise around the cylinder 
(from number 1), when viewed from above. The cables 
carry colour-coded sleeves to indicate the phase and 
when connected correctly should follow the following 
sequence. Red/Yellow/Blue/Red/Yellow/Blue when 
viewed clockwise from the top. (NB The colour 
sequence for two electrode cylinders will be Red/Blue. 

 

 

12. 

The connections to the cylinder should be routed in as 
close as possible to their original route.

 

 

2.1.2 

Typical Cylinder / Electrode Layouts

 

  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

See technical data for cylinder size fitted to your unit

Fig 1 

Full Pin

1

2

1

Full Pin

2

3

1

Full Pin

3

5

2

4

6

Size 1 / 2 (2 electrode) 

Size 3

 (3 electrode)

Size 4  (3 electrode) 

Size 4 (6 electrode) 

Component Identification 

Summary of Contents for LEC05

Page 1: ...the requirements of the RoHS Directive 2002 95 EEC This product will meet the requirements of the Low Voltage Safety Directive 2006 95 EEC and the EMC Directive 2004 108 EEC when installed in accorda...

Page 2: ...l Control 12 1 6 3 Control Signal Selection 12 1 6 4 On Off Control 12 1 6 5 Sensing Head 13 1 6 6 Security Circuit E P O Shutdown 13 1 6 7 Load Shed Option 13 1 6 8 Master Slave System 14 2 0 Start U...

Page 3: ...the terminals and contactor are tight Check that the transformer primary winding connection is correct for the supply voltage at Vapac terminals A1 A2 The Vapac transformer must not be used to power o...

Page 4: ...the unit in position Don ts Don t mount the unit close to sources of strong electro magnetic emissions e g variable speed lift motor drives kVa transformers etc Don t mount the unit in an unventilate...

Page 5: ...late 120 X 120 Gland Plate 120 X 120 Left Top View Showing Steam O let position Below Rear View showing wall mounting points Left Bottom View Showing F Feed connection BSP male connection for flexible...

Page 6: ...nit of 300mm Do use the full height available between the unit and steam pipe to provide maximum slope min 12 20 for condensate to drain back to the steam cylinder or down to a condensate separator Al...

Page 7: ...and to effect a seal If water seepage occurs undo the nut to wipe the washer clean and re seat it 1 3 2 Drain connection General Do s Do ensure metal drain and supply water pipework is grounded electr...

Page 8: ...sition marked with the supply Voltage that is to be connected between VAPANET power terminals A1 and A2 The transformer primary circuit terminal positions are clearly marked 200V 230V 380 415 440V If...

Page 9: ...547 Normally open when unit is in standby or fault not running If the unit is part of a master slave system or network the run fault outputs can be selected via keypad display as either network system...

Page 10: ...used to ensure cables are held securely at the entry position All Vapac cabinets are equipped with a removable gland plate The installing electrician should remove this and take it to a work bench to...

Page 11: ...h 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph No of electrodes 3 3 3 3 3 3 6 6 3 3 3 3 Full load Current per cylinder A 46 5 40 5 24 5 23 5 22 5 21 5 78 68 41 39 37 5 35 5 Maximum overcurrent per cylinder A 53 475 46 575...

Page 12: ...by either a potentiometric signal a lonworks network signal or by one of 6 standard proprietary DC analogue signals Input signal Potentiometric control 0 5V 0 10V 0 20V Actually 0 18V not phase cut 2...

Page 13: ...10 will prevent any unit operation including frost protection 1 6 7 Load Shed Option This can only be evoked via a display either hard wired or hand held When this option is selected making the conne...

Page 14: ...le in each unit of the system including the master xxxxxx xxxxxx xxxxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxx Esc Vapac J2 Vapac part no 1150631 CR1 Net J1 Vapac PART...

Page 15: ...procedure by selecting the preferred language Attaching the control PCB to the Display nominating the type quality of the supply water nominating the control signal or Vapac sensor when being used Wh...

Page 16: ...ose clip 1 and disconnect the steam hose 4 from the top of the cylinder 6 Using a twisting movement lift the cylinder clear of its seating in the feed drain manifold and carefully remove the used cyli...

Page 17: ...ollows Turn off the water supply to the Unit Undo the nylon nut connecting the flexible connection to the valve inlet The strainer can be removed using long nosed pliers to grip the centre flange prov...

Page 18: ...User LED 2 Description OFF OFF Cylinder 1 and Cylinder 2 in shutdown Or Cylinder 1 in standby and Cylinder 2 in shutdown OFF RED Flashing 1 second period Cylinder 1 and Cylinder 2 in standby Green Am...

Page 19: ...0 50 Timed Drain down Used to drain all the water from the cylinder if the unit remains on standby for longer than a preset but adjustable time period For information on setting these options please s...

Page 20: ...operational level of water in the cylinder Switch unit on and check that the display indicates Vapac on line Apply the voltmeter set to the ful line Voltage across the output terminals of the SSR bein...

Page 21: ...A3 A1 2A Net CR1 CR4 v 0v 2 3 8 9 6 4 5 7 CR6 9v AC Fused Supply Part Number 1150631 1 Blue 1 Brown 2 Blue 2 Brown TO SHEET 3 of 3 SEE NOTE 1 BLUE RED 70 VA Auto wind TAPPING IS A 230 VOLT Red 9v AC...

Page 22: ...dc feed DO 6 DI 6 CYL 2 SSR LEC 9v dc feed DO 5 DI 5 CYL 1 SSR AI 1 V or mA INPUT Demand POT 0v dc Demand POT 5v dc AI 2 CYL 1 CURRENT INPUT AI 1 Ref AI 2 Ref Black Red Black Red White Violet Red Blac...

Page 23: ...hite Pink Pink Violet Pink Pink Pink Violet Pink Pink ANALOGUE INPUT 8 0v COM AI 8 ANALOGUE INPUT 7 0v COM AI 7 ANALOGUE INPUT 6 0v COM AI 6 0v COM AI 5 ANALOGUE INPUT 5 Bond Earth 0V Control Fuse Vio...

Page 24: ...Yellow 26 Blue LE05P and LE09P A1 Ph 1 A2 Ph 2 or N Three Electrode E1 E2 E3 cylinder for SINGLE CYLINDER UNIT LE18 LE30 high voltage TWIN CYLINDER UNIT LE60 High voltage cylinder 1 CONNECTED TO A3 FO...

Page 25: ...oltage and LE60P low voltage SUPPLY DETAILS PLEASE REFER TO FOR ELECTRICAL LOADS AND POWER THE VAPENET LE OPERATION AND MAINTENANCE MANUAL latest Edition CONNECTED TO N FOR 380 440 V 3 PHASE SUPPLY CO...

Page 26: ...LY DETAILS PLEASE REFER TO FOR ELECTRICAL LOADS AND POWER THE VAPENET LEC OPERATION AND MAINTENANCE MANUAL latest Edition Neutral Earth Supply A 3 Phase LOW VOLTAGE AND LEC45 CYLINDER 2 VAPAC SIX ELEC...

Page 27: ...0 LV LEC45 CABLE SIZE in mm2 TRI RATED CABLES SUPPLY DETAILS PLEASE REFER TO FOR ELECTRICAL LOADS AND POWER THE VAPENET LEC OPERATION AND MAINTENANCE MANUAL latest Edition Neutral Earth Supply A 3 Pha...

Page 28: ...e constricted leading to excessive pressure in the steam lines N B Standard steam distribution pipes are manufactured such that any condensate is drained back towards the Vapac steam cylinder Reverse...

Page 29: ...ates that a reverse slope steam pipe is required This is fitted with a drain point to allow condensate to be taken away to a convenient drain Figure 2 shows recommendations on how to space one or more...

Page 30: ...ndensate drain connection 3 Care should be taken to support steam hose sufficiently such that no kinks are formed which would flood with condensate causing the bore of the tube to become constricted l...

Page 31: ...Made in England by Vapac Humidity Control Ltd June 2004 Vapac Humidty Control Ltd reserve the right to change the design or specification of the equipment described in this manual without prior notic...

Reviews: