LExx-SR weights
The unit dry weight is the delivered unit with no water in the unit, the wet weight is the operational
weight when the unit is running.
1.3
Positioning the steam pipes
Do's
Do
use Vapac steam hose or well insulated copper pipe
Do
keep steam hose as short as possible (under 2m for max efficiency).
Do
arrange to have a vertical rise immediately over the unit of 300mm
Do
inject the essence into the steam line below the level of the cylinder and ensure that it can flow
freely out with the flow of steam. Any restrictions in flow will result in the essence solidifying and
causing a restriction to flow of steam.
Do
add extra insulation to steam hose for longer runs (2m-5m) and in cold ambient conditions to avoid
excess condensate and reduction in delivered output.
Don'ts
Don't
allow steam hose to develop kinks or sags.
Don't
include horizontal runs or 90o elbows in the steam line.
Vapac model
Dry Kg
Wet Kg
LE18-SR
39
65.5
LE30-SR
40
66.5
LE45-SR / LE55-SR
45
72