Section General
Page 5 of 24
18 Feb 2015
1.0 Installation
Do’s
Do
mount the unit as close to the steam distribution pipe(s) as possible.
Do
mount the unit at a height convenient for reading the display window.
Do
ensure adequate side ventilation (min 80 mm).
Do
ensure adequate service access to the front of the unit (min 1000 mm).
Do
ensure adequate service access below the unit (min 1000 mm).
Do
ensure that the holes in the rear top panel remain unobstructed to allow a free flow of air.
Do
use the marking on the side of the carton as a template to mark the mounting hole positions.
Do
remove the cylinder, if necessary, to access the mounting holes in the back of the steam section.
Do
use M6 projecting type wall bolts or equivalent to mount the unit in position.
Don’ts
Don’t
mount the unit close to sources of strong electro-magnetic emissions e.g. variable speed lift
motor drives, kVa transformers etc.
Don’t
mount the unit in an unventilated enclosure.
Don’t
mount in a position requiring ladder access to the unit.
Don’t
mount the unit behind a false ceiling or other situation where an unusual malfunction (e.g. water
leak) would cause damage.
Don’t
mount the unit in an area which will be hosed down.
Don’t
install the unit where the ambient temperature can exceed 35°C; or fall below 5
°
C.
Don’t
mount the unit inside a cold-room or other place where temperature and humidity conditions can
cause condensation on electrical components.
Don’t
mount the unit where the sound of a contactor opening/closing and water flow in a pipe would
be unacceptable e.g. libraries, private apartments, etc