1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example:
Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2,560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example:
2,560 cu. ft. (volume of space) x
20 = 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free fireplace
__________ Btu/Hr
Gas water heater*
__________ Btu/Hr
Gas furnace
__________ Btu/Hr
Vented gas heater __________ Btu/Hr
Gas fireplace logs
__________ Btu/Hr
Other gas appliances* + __________ Btu/Hr
Total
=
__________ Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater
__________ Btu/Hr
Vent-free fireplace +
__________ Btu/Hr
Total
=
__________ Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
_______ Btu/Hr (maximum the space can
support)
_______ Btu/Hr (actual amount of Btu/Hr
used)
Example:
51,200 Btu/Hr (maximum the
space can support)
71,500 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a confined space
because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support. You
must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconfined space, remove door to adjoining
40,000
31,500
71,500
AIR FOR COMBUSTION AND VENTILATION
Continued
Figure 2 - Ventilation Air from Inside Building
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
room or add ventilation grills between rooms.
See
Ventilation Air From Inside Building
.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors
, page 8.
C. Install a lower Btu/Hr fireplace, if lower Btu/
Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support,
the space is
an unconfined space. You will need no additional
fresh air ventilation.
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combus
-
tion and ventilation air shall be
provided by one of the methods
described in the
National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the
International Fuel Gas Code,
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the floor on the
wall connecting the two spaces (see options 1
and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Fol
-
low the
National Fuel Gas Code ANSI Z223.1/
NFPA 54 Air for Combustion and Ventilation
for
required size of ventilation grills or ducts.