2
SPECIFICATIONS
AC Input - Power Supply
Type
Universal Input
Input Voltage / Frequency
120 – 277 VAC 50-60Hz
Input Power
<16W
Connection Type
0.20” pitch removable plug
Connection Rating
300V 10A
Input / Output Connections (Low-voltage)
Station Bus Connection
24V / 36V Station Bus
Station Bus Wire Specification
2C, 16AWG / 1.31mm2, twisted, nonshielded, <30pF per foot. Separate a
minimum of 12” / 30.5cm from other parallel communication and/or high-
voltage runs
Station Wiring Configuration
Daisy-chain, Star, Branch
Station Equivalent InFusion
0.35W on IC-24 / 0.55W on IC-36
Auxiliary Inputs
4 Dry contacts (3 and 4 may be used for an IR receiver and light sensor
respectively)
Override Inputs
Yes - All ON or All OFF contacts
Low-voltage Output - PWM Low
Specification
IEC 60929 Annex E
Number of Outputs
4
Output Voltage
12V (Source only)
Output Current
100mA per channel, 400mA total
Loads Per Output
50@2.0mA per load (typical)
Resolution
>1024 steps
Duty Cycle
Variable 0% to 99.9%
Frequency
760Hz
Connection Type
0.20” Pitch removable plug
Connection Rating
300V 10A
Connection Torque
4.4 inch pounds
Low-voltage Output - 0-10V
Specification
IEC 60929 Annex E
Number of Outputs
4
Output Voltage
0-10V @ 100mA sink or source
External Source Voltage
Typical 10V / Maximum 20V
Loads per Output
50@2.0mA per load (typical)
Resolution
>1024 steps
Connection Type
0.20” pitch removable plug
Connection Rating
300V 10A
Connection Torque
4.4 inch pounds