OVERVIEW
The Vantage LVOS-0-10-PWM-1 (LVOS) has four PWM and four analog
low-voltage outputs along with four high-voltage relays. All twelve
connections are independent from each other. The station is powered from
a universal input of 120-277 VAC 50/60Hz source. The high-voltage relays
are isolated from the station’s high-voltage power supply. All outputs can be
manually controlled and monitored from the front of the station. An Override
switch may be connected allowing all the low-voltage loads and high-
voltage relays to be ON or OFF for fail-safe applications. The station comes
housed in a custom metal enclosure or may be ordered separately for
installation into Vantage’s IAUX enclosure. Communication to the Vantage
System is via Station Bus.
*WARNING:
This is not a DIN station and is not designed for DIN
rail. Vantage’s auxiliary enclosures, IAUX-2 / IAUX-4 and LCAP44A-6
enclosures are ordered separately.
FEATURES
•
4 PWM, low-voltage outputs
•
4 Analog, 0-10 low-voltage outputs
•
4 High-voltage relays – tied to low-voltage
outputs in Design Center
•
Twelve membrane style actuators and LED
status indicators
•
High resolution performance when dimming
•
Communicates via Vantage Station Bus
•
Housed in a custom, UL rated enclosure
- Part #LVOS-0-10-PWM-1 includes station
and enclosure
•
Enclosure configurations
- IAUX-2 – up to six stations per enclosure
- IAUX-4 – up to ten stations per enclosure
•
Override switch connections for ON and OFF
states of all loads collectively
General
Dimensions, HWD
9” x 10.5” x 2.75” (22.86cm x 26.67cm x 6.98cm)
Cover Dimensions, HWT
9.75” x 11.25” x 0.6” - 1/16” Thick (24.77cm x 28.58cm x 15mm-thick)
Station Only Dimensions, HWD
3.32” x 10.34” x 2.667” (8.43cm x 26.26cm x 6.77cm)
Weight with Box
5.85lbs (2.65kg)
LED Indicators
Microprocessor Status, Configuration, Loads
Ambient Operating Temperature
32-104°F / 0-40°C
Relative Humidity
Maximum 90%, non-condensing
Firmware
Upgradeable via Station Bus
Cooling
Convection
Manual Control
Overlay with control/status for each output
FreeRTOS™
Real-time scheduling provided by FreeRTOS (www.freertos.org)
Part #
Description
LVOS-0-10-PWM-1
Station with Single Enclosure: Low-Voltage
Output Station (PWM and 0-10) 120V-277V -
Comes in a custom Vantage supplied, UL rated
enclosure
LVOS-0-10-PWM-P-1
LVOS-0-10-PWM Station only - For installing
in UL rated IAUX-2, IAUX-4, or LCAP series
enclosures*
TWO WAYS TO ORDER