background image

INCORPORATED

®

                                                                         Installation 

 

ITC-Series

 Inverter 

Page 23 

 

 

 

 

 

Owner’s Manual 8/5/17 

Failure to connect the chassis bonding lug to the chassis of the vehicle, the installation's grounding system, 
or to earth ground may result in a lethal shock hazard. 

 

AC Wiring Procedure (refer to Figure 3-1) 

Warning:

  Make certain that the AC field wiring (upper right of the wiring compartment) and the Signal wiring 

(at the lower right of the wiring compartment) are kept separate to avoid any problems or conflicts with 
code.  Make certain to route the Signal wires out of the provided port (lower most on the right side of 
the  unit).      This  is  to  insure  that  there  are  no  problems  that  may  arise  from  the  poor  insulation 
properties  of  most  signal  level  wire.    Make  certain  that  the  auxiliary  contact  and  option  wiring  are 
routed below the barrier, and the AC Power Wires above the barrier. 

Step 1:   Connect  the  AC  output.  Remove  the  front  cover  to  expose  the  AC  input  and  output  terminal  strips. 

I

dentify the right terminals labeled “AC Output”. Insert the output field wires through the nearest (to the 

board) strain relief into the AC wiring compartment. Tighten the strain relief. Connect the copper field 
wires to the proper AC output terminals and tighten to 9 lb-in max.  

Warning:

  Do  not  attempt  to  use  a  stranded  wire.    Stranded  wire  has  a  tendency  to  break  off  some  of  the 

strands and will drop into the unit causing possible failures.  If a stranded wire is used, the appropriate 
“ring terminal” must be used. 

Step 2:  

Connect  AC  Input.  Identify  the  terminal  strip’s  terminals  labeled  “AC  Input”.  Insert  the  field  wires 

through the (closest to the front panel) strain relief into the AC wiring compartment. Tighten the strain 
relief.  Connect  the  copper  field  wires  to  the  proper  AC  input  terminals  and  tighten  to  9  lb-in  max. 
Replace the front cover. 

Warning:

  Do  not  attempt  to  use  a  stranded  wire.    Stranded  wire  has  a  tendency  to  break  off  some  of  the 

strands  and  will  drop  into  the  inverter  causing  possible  failures.    If  a  stranded  wire  is  used,  the 
appropriate “ring terminal” must be used. 

Step 3:   Connect Bonding Lug. Use a 8 AWG or larger copper conductor to connect the chassis bonding lug to 

the chassis of the vehicle, the installation’s grounding system, or to earth ground. 

Step 4:   Verify Installation. Verify all connections are tight and secure for maximum performance. 

System Start-up and Testing 

Step 1: 

Completely  install  the  ITC-Series  Inverter/Charger  following  the  system  design  considerations  and 

instructions provided previously in this manual. 

Step 2: 

Place the System Power On/Off switch located on the front of the inverter in the OFF position. 

Step 3: 

Verify that the external GFCI breaker is reset and connect an AC load, such as a 100-Watt light. Note: 

some GFCI’s require power to be applied before they will reset. 

Step 4: 

Turn ON the battery DC power to the inverter. 

Step 5: 

Turn ON the AC shore power (or generator) to supply the AC input power to the system 

Step 6: 

Place the System On/Off Power switch located on the front of the inverter to the ON position. 

Step 7: 

The  Lights  on  the  Control/Display  Unit  on  the  front of the inverter should come ON, by doing a lamp 

test. 

Step 8: 

Disable the Charger Operation of the unit by pressing the Charger ON/OFF button once if the Charger 

LIGHT is On or blinking.  This turns the charger function OFF. 

Step 9 

If  the  Inverter  LIGHT  is  not  On  or  blinking,  enable  the  Inverter  Operation  of  the  unit  by  pressing the 

Inverter ON/OFF button once.  This turns the Inverter function ON. 

Step 10 The  AC  output  test  light  should  come  ON,  indicating  the  presence  of  shore  power  and  correct 

operation of the AC transfer switch. 

Summary of Contents for SP00175

Page 1: ...Manual 8 5 17 ITC Series Inverter Charger System Models SP00175 SP00176 ITC12 2100 ITC12 3200 and SP00172 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 614 771 2718 1 800 ACPOWER www van...

Page 2: ...INCORPORATED ITC Series ITC Series Inverter Page 2 8 05 17 Notes...

Page 3: ...WIRING IDENTIFICATION 18 AC INPUT OUTPUT WIRING 18 DC BATTERY WIRING 18 FRONT PANEL CONTROL DISPLAY OUTLET 19 SYSTEM ON OFF SWITCH 19 REMOTE SIGNAL CONTACTS 19 INSTALLATION 19 BASIC GUIDELINES 19 DC W...

Page 4: ...7 Figure 1 4 6 Suspended Dimensions in Inches 11 F 8 Figure 1 4 7 Bottom Mount Dimensions in Inches 11 F 9 Figure 1 4 8 Control Display Unit Dimensions in Inches 11 F 10 Figure 1 4 9 Customer Terminat...

Page 5: ...e cover of this manual System Features and Specifications General Description The ITC Series system consists of a DC to AC true sine wave inverter a battery charger an automatic AC transfer switch and...

Page 6: ...lts This will alert the user to take appropriate measures to avoid shutdown of the Inverter at 10 5 21 0 VDC The SP00172 offers a Fan On contact instead of the Low Battery contact for turning on an ex...

Page 7: ...Surge Capacity 25 C 3 sec 6400 watts DC INPUT Operating Range 10 5 to 17 Volts 21 0 to 31 Volts No Load Inverter ON 4 amps 3 amps No Load Inverter OFF 0 30 amps 0 30 amps Full power 208 amps 350 amps...

Page 8: ...6 7 8 9 4 5 FRONT VIEW 13 2 14 15 16 10 LEFT SIDE VIEW RIGHT SIDE VIEW 11 12 15 16 OPTIONS CABLE ENTRY CHASSIS GROUND ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 DESCRIPTION BATTERY TERMINAL ACCESS REMOTE...

Page 9: ...when enabled but not on 2 Inverter On Off Button Enables Disables Inverter Function 3 Charger Indicator Light Solid when on flashes when enabled but not on 4 Charger On Off Button Enables Disables Cha...

Page 10: ...allowing access to user AC and control terminals through a removable front cover ACCESS PANEL REMOVABLE FROM FRONT WHEN UNDER TABLE MOUNTED DOCKED DISPLAY CONTROL PANEL DC TERMINATIONS POWER ON OFF SW...

Page 11: ...8 5 17 18 10 7 8 19 1 4 13 5 8 16 3 4 8 1 8 7 5 16 8 3 4 ITC DIMENSIONS FOR SUSPENDED MOUNTING F 7 Figure 1 4 6 Suspended Dimensions in Inches 19 1 4 18 10 7 8 16 3 4 13 5 8 7 5 16 8 ITC DIMENSIONS F...

Page 12: ...ITC Series Inverter Page 12 8 05 17 F 9 Figure 1 4 8 Control Display Unit Dimensions in Inches Overload Overload LowBattery Bulk Fault Fault INCOR PORATED Inverter On Off Charger On Off 3 78 3 50 3 3...

Page 13: ...l be steadily on when the unit is in the Inverter or Charger mode These Inverter and Charger lights will blink if the mode is not currently on but are enabled Example The Inverter light will blink whe...

Page 14: ...temperature will shut down system Overheat The SCR plate or power brick overheating will cause the system to shutdown If the unit has faulted there are the two following options 1 Auto restart After...

Page 15: ...uring the Equalize Cycle the battery is charged at the Absorption Charge Amps setpoint and the Equalize Voltage 15 5 30 0 VDC setpoint The Equalize Charge Cycle provides a deliberate overcharging of t...

Page 16: ...ally the temperature sensor part number is D012684 and the cable part number is D012638 Automatic Power Management APM A key feature of the battery charger operation is Automatic Power Management APM...

Page 17: ...le Control Display Units Note The figure below is also available on the Rear of the Control Display Unit on 12V units ON O OFF 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 5 O O O O O O O O 6 O O O O O...

Page 18: ...rtment is a terminal strip for making AC input and AC output connections P14 and P15 NOTE The AC output voltage and the required AC input voltage of the ITC is 120 VAC 60Hz DC Battery Wiring A DC wiri...

Page 19: ...is provided terminal 6 with a current limiting resistor integral to the circuit INSTALLATION Unpacking the Inverter Inspect the shipping container and equipment for loose or damaged parts If any damag...

Page 20: ...allations do not use the vehicle chassis as the DC negative conductor Use a cable the same size as the DC positive to go directly from the inverter to the battery negative 4 Route the AC and DC power...

Page 21: ...nd negative cables enter the compartment through separate strain reliefs located at the right front of the unit WARNING Never make electrical connections live Make the connections to the inverter firs...

Page 22: ...vided by others to comply with the National Electric Code NFPA 70 2 AC Wire Size To properly size the AC input and output wiring the installer must consider the inverter output capability the inverter...

Page 23: ...ield wires to the proper AC input terminals and tighten to 9 lb in max Replace the front cover Warning Do not attempt to use a stranded wire Stranded wire has a tendency to break off some of the stran...

Page 24: ...attery Note the keyed BTS cable has same connector on both ends so cable connector orientation does not matter Make sure cable does not come into contact with sharp edges and is secured with nylon tie...

Page 25: ...nces that contain electronic power supplies e g computers TVs and VCRs The square wave is appropriate when operating AC loads such as resistive heating devices Inverter Sizing Output Power Rating Powe...

Page 26: ...parated into two categories according to their use engine cranking batteries and deep cycle batteries The engine cranking battery is specifically designed to supply hundreds of amps for a short period...

Page 27: ...cases this may be true but in general the battery may be made up of several individual batteries electrically connected together to form a Bank of batteries Batteries can be connected in series parall...

Page 28: ...installation The Battery System is responsible for supplying all of the DC power required by the inverter The system normally consists of the primary charger engine alternator or photovoltaic array a...

Page 29: ...the type and model of battery you are using This is because battery charging parameters such as bulk absorption float and equalize voltages vary from one manufacturer to another and that gel cell batt...

Page 30: ...corrosion free 2 Check air ventilation openings for dust and other obstructions 3 Examine receptacle indicators and switches for cracks and breaks in insulation material Trouble Shooting The Unit does...

Page 31: ...quasiwave inverters with load demand active you will need to turn off the inverter and then turn the inverter back on to reset the GFCI receptacle within 5 seconds before the inverter goes back into l...

Page 32: ...nverter Page 32 8 05 17 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 1 800 AC POWER 1 800 227 6937 Tel 614 771 2718 Fax 614 771 4904 www vanner com e mail pwrsales vanner com Manual Num...

Reviews: