Acoustic and Optical Signals
Acoustic Signals in Stand-alone Operation Mode
Signal
Symbol
Description
One long signal
♫
Error - unknown card, access denied.
Two long signals
♫ ♫
Attempt to assign the same function for two different
input lines.
Two bursts, each
burst with 3 short
beeps
♪♪♪ ♪♪♪
Command successfully completed (OK signal).
Two short beeps
♪♪
Prompt signal, the reader is waiting for the next part of
the command to be entered. This signal is intended to
invite the programmer to proceed with next program-
ming steps.
One long signal con-
tinuously repeated
♫ ♫ ♫ ♫…and
so on
Memory contents corrupted or Master/Installer Card
not programmed - Memory Reset necessary. This sig-
nal is accompanied by the steady lit LED SYSTEM.
Legend:
♫ - one long audible signal
♪ - one short audible signal (beep)
LED Indications in Stand-alone Operation Mode
LED
STATUS
LED
OPEN
LED
SYSTEM
Description
Green
—
—
The reader is in DISARMED State.
Red
—
—
The reader is in ARMED State.
Red
Green
—
The reader is in User Programming Mode.
Green
Green
—
The reader is in Installer Programming Mode.
—
—
Orange flash-
ing
Waiting for the user to enter the next part of the com-
mand or programming function.
—
—
Orange, sin-
gle flash
A user card has been read.
—
Green
—
The door lock is activated, this LED remains on as
long as the door lock is energized.
—
Green flash-
ing
—
The reader is waiting for a user to read his card (e.g.
when Toggle Card is used to change ARMED/DIS-
AMED Mode).
—
—
Steady
The reader has detected a problem (memory contents
is corrupted or a Master/Installer Card is not pro-
grammed).
NOTE
When the ARS6311-RX operates with a second ARS6311-RX (for two-way control of the door) the