2 Installation
The ACTpro-100 door stations are for indoor installation only and must be installed as permanently
connected equipment.
Reset the ACTpro-100 door station to its factory default condition before installation. To do this, power the
unit up with ALL switches in the OFF position. The unit will beep after 3 seconds. The unit is now
defaulted. Set the DIP switches to the appropriate address.
If using the ACTpro-1002A, Vanderbilt recommend that an external mains disconnect device is fitted
before installation, and you should ensure that the mains supply to the controller is disconnected during
installation.
Mains power should be connected by a licensed electrician in accordance with local/national codes.
2.1 Wiring
A
Door contact
F
Vanderbilt reader wire colour coding
B
Door push button
G
Important:
Always place varistor across lock terminals.
C
From previous door or controller
H
Double pole Break Glass / Emergency Door Release
When the Break Glass is not activated the B/GL input pin is
held low at 0 volts. When the Break Glass device is
activated the B/GL input pin will lose the 0 volts (goes high)
and report a Break Glass event.
D
To next door
J
DIP switches for door station addressing. See
E
Break glass monitoring, normally closed