Note:
The red Fault LED may be illuminated (dependent upon model) to indicate that no battery has
been connected. This is normal.
3. Verify load is operating correctly.
4. Disconnect mains power.
2.3.4 Standby Battery
Note:
Ensure batteries being fitted to this unit are in good condition
1. Connect battery leads to battery, ensuring correct polarity of battery connections. Vanderbilt
recommend using a 7Ah battery.
2. Apply mains power and check that the green Mains LED is on.
3. Disconnect mains power.
4. Check that the batteries continue to supply voltage and current to the load.
The green Mains LED should be off.
Note:
Batteries must have sufficient charge to supply the load.
5. Reconnect mains power.
The green Mains LED should be on.
6. Remove Load fuse and check that the red Fault LED is on (dependent on model).
2.3.5 Tamper
A tamper condition is reported in software.
1. Check that the tamper switch is reported in the software as:
l
Closed when the enclosure is mounted on the wall, lid is closed, and the lid screw is fitted.
l
Open when the lid is open.
2. Close cover and secure using fastening screw(s) provided.