
Label
Description
Label
Description
D
Vanderbilt reader wire colour coding
3.1.1 Wiring exit readers
For clock and data readers, wire exit readers in parallel but leave the sense line unconnected.
For Wiegand readers, wire the DATA 0 of the exit reader to the SENSE pin on the ACT365-ACU and
DATA 1 to the CLOCK/D1 pin on the ACT365-ACU.
Max length: 100m with 12V DC
Cable: 8 core screened Belden 9504 or equivalent
3.2 Fire override configuration
To release doors on fire alarm activation:
1. On the ACT365 customer portal, select the site from the site picker.
2. Under
Manage Sites > Site Settings
, select the door group containing fire doors from the
Fire
Door Group
drop-down list, then click
Save
.
3. Wire the fire alarm panel (A) to the controller as shown:
While the 0V signal is maintained at the AUX input on Door 1, the doors in the
Fire Doors
group maintain
normal operation.
When the 0V signal is removed, the doors in the
Fire Doors
group are unlocked. The fire doors remain
unlocked until the 0V signal is restored.
3.3 Interlock/airlock configuration
To allow only one door to open at a time:
1. Wire the airlock doors.
Link OP3 and AUX I for each new door. For example, the following diagram shows how to interlock
two doors: when the first door is open, the second door is locked, and vice versa.
ACT365-ACU / ACT365-ACU2A / ACT365-ACUPoE – Installation Instructions
Wiring
© Vanderbilt 2019
12
A-100521-c
15.03.2019