9.2 Tests and environmental
conditions
9 Technical data
Technical description
194
VAMP 24h support phone +358 (0)20 753 3264
VM59.EN001
9.2.
Tests and environmental conditions
9.2.1.
Disturbance tests
Test
Standard & Test class / level
Test value
Emission
EN 61000-6-4 / IEC 60255-26
- Conducted
EN 55011 class A / IEC 60255-
25
0.01 - 30 MHz
- Emitted
EN 55011 class A / IEC 60255-
25 / CISPR 11
30 - 1 000 MHz
Immunity
EN 61000-6-2 / IEC 60255-26
- 1Mhz damped oscillatory
wave
IEC 60255-22-1
±2.5kVp CM, ±1kVp DM
- Static discharge (ESD)
EN 61000-4-2 class IV / IEC
60255-22-2
8 kV contact, 15 kV air
- Fast transients (EFT)
EN 61000-4-4 class IV / IEC
60255-22-4 class A
±4 kV / (±2 kV signal ports),
5/50 ns, 5 kHz
- Surge
EN 61000-4-5 class III / IEC
60255-22-5
2 kV, 1.2/50
s, CM
1 kV, 1.2/50
s, DM
- Conducted HF field
EN 61000-4-6 class III / IEC
60255-22-6
0.15 - 80 MHz, 10 Vemf
- Emitted HF field
EN 61000-4-3 class III / IEC
60255-22-3
80 - 2700 MHz, 10 V/m
- Voltage interruptions
EN 61000-4-29 / IEC 60255-11
30%/1s, 60%/0.1s,
100%/0.05s
- Voltage alternative
component
EN 61000-4-17 / IEC 60255-11
12% of operating voltage
(DC) / 10min
- Voltage dips and short
interruptions
EN 61000-4-11
30%/10ms, 100%/10ms,
60%/100ms
>95%/5000ms
- Power-frequency magnetic
field
EN 61000-4-8
300A/m (continuous),
1000A/m / 1-3s
- Pulse magnetic field
EN 61000-4-9
1000A/m, 1.2/50
s