VAMP Ltd
Power monitoring unit
Operation and configuration
VAMP 260
VM260.EN004
Vamp 24h support phone : +358 (0)20 753 3264
25
5.5.
Configuring analogue outputs AO
In the main menu ANALOG OUTPUTS the values of the
analogue outputs AO1 - AO4 are shown. E.g. to test the outputs
the ‘Force’ function can be used to manually control the output
channels.
1.
In the sub menu AO LINKS the measured and calculated
values, e.g. active power (P) are linked to one of the
analogue outputs AO1 - AO4, e.g. AO1. See list available
variables below for values that can be linked.
2.
In the sub menus AO1-AO4 SCALING the configurations of
the analogue outputs can be set.
3.
In the sub menus AO1-AO4 EXCEPT.CTRL the
configurations of the exceptional analogue outputs can be
set.
Note:
AOx SCALING and AOx EXCEPT.CTRL menus for each AO
follow each other.
Available link variables
•
P, Q, S
•
f
•
PF
•
Cos
ϕ
•
IL1, IL2, IL3
•
U12, U23, U31
•
UL1, UL2, UL3
•
IL
•
U, Uphase
•
DI1 – DI6
5.6.
Setting user averages
In the main menu USER’S AVERAGES 1 and in the first sub
menu USER’S AVERAGES 2 the values of signals Ave1 - Ave 8
defined by user configuration can be read.
1.
In the next eight sub menus MEAN VALUE 1 - MEAN
VALUE 8 the customized average measurements
parameters Time, Unit and Lnk can be set and the State
read.
2.
Setting the Lnk parameter any one of the available
variables of the relay can be set.