VAMP 260
Power monitoring unit
Operation and configuration
VAMP Ltd
20
Vamp 24h support phone : +358 (0)20 753 3264
VM260.EN004
DO
Pick RELAY OUTPUTS 1
Enable forcing
T1
T2
A1
A2
Force
0
0
0
0
OFF
Figure 4.4-1 Selection of the Force function.
4.
Push the ENTER key.
5.
Push the UP or DOWN key to change the "OFF" text to
"ON", i.e., to activate the Force function.
6.
Push the ENTER key to return to the selection list. Choose
the signal to be controlled by force with the UP and DOWN
keys, for instance the T1 signal.
7.
Push the ENTER key to confirm the selection. Signal T1
can be controlled by force.
8.
Push the UP or DOWN key to change the selection from "0"
(not alert) to "1" (alert) or vice versa.
9.
Push the ENTER key to execute the forced control operation
of the selected function, e.g., making the output relay of T1
to pick up.
10.
Repeat steps 7 and 8 to alternate between the on and off
state of the function.
11.
Repeat steps 1...4 to exit the Forced control function.
12.
Push the CANCEL key to return to the main menu.
4.5.
Setting range limits
Note!
If parameters requiring a numerical setting value are given
out-of-range settings, a fault message will be obtained when
the setting is confirmed with the ENTER key. Adjust the
setting to within the allowed setting range. The allowed setting
range is shown in the display in setting mode:
1.
Push the INFO button.