24
Operation Check and Aeration Adjustment
Turn the
replace up and down using the remote control to con
rm
that the full range of inputs is achieved.
Light the
re and allow to warm up for 10–15 minutes to evaluate
the
ame picture.
The burner is equipped with an adjustable air
shutter to control primary aeration. See
gures below. The shutter is
factory-set at an aeration gap, which will give optimum performance
for the vast majority of installations. In a few unusual installations,
ame picture may be improved by adjusting the aeration. The need
for adjustment should be determined only by operating the appliance
with the ceramic fuel effects and window installed.
Increasing aeration
will cause the
ame to appear more
transparent and blue making the ceramic fuel effects
glow more.
Decreasing aeration
will cause the
ames to appear
more yellow or orange making the fuel effects glow less.
Too little aeration may result in black carbon
forming and dropping into the
fi
rebox.
Air Shutter in
Open Position
Air Shutter in
Closed Position
Air Shutter
Air Shutter Retainer
Air Shutter Components
To check vent action,
hold a match or
source of smoke in
front of Draft Channel
(smoke should be drawn
inward)
Draft Channel
Draft Channel
Bracket secured
by 2 screws
RH side of fireplace
Vent Switch
Vent Switch
Bracket
This unit is equipped with a vent safety switch, located
on the right side of the draft hood, which will shut the
burner off if the vent is not functioning properly. Use
a match or a source of smoke at the front of the draft
channel to check direction of
ow in the vent. Access to
the vent switch for servicing is shown below.
Vent Check
Vent Safety Switch Location
Vent Check
QUALIFIED
INSTALLER
Summary of Contents for Retrofire RF24XBN
Page 30: ......