4006630-01

This appliance is certifi ed for use from 0-4500ft. For 
altitudes above 4500ft see local codes.

Kit Contents

•  1 Pilot injector (see chart below)
•  1 Burner
•  1 Main burner injector (see chart below)
•  1 Minimum rate by-pass screw (see chart below)
•  1 Set of conversion labels
•  1 Set of air shutters

Tools Required

•  Wrenches, to disconnect gas line
•  Phillips (+) screwdriver, to remove burner module
•  Small jewelers size fl at blade screwdriver, to set pressure
•  Small fl at blade screwdriver, to release pressure tap on 

valve

•  Needle Nose Pliers, to remove by-pass screw
•  Hex Allen wrench, 4 mm or 5/32”, to remove pilot injector
•  Special 2-pin screwdriver tip, supplied with kit, to 

remove valve cover

•  Manometer, to set pressure

Fireplace Models

RF24JBN

RF24JBP

Gas

Natural

Propane

Altitude (Ft)

0–4,500 Feet

Input Max. (Btu/h)

20,000

18,000

Input Min. (Btu/h)

12,500

12,500

Manifold pressure (in w.c.)

3.2

9.5

Min. Supply pressure 
(in w.c.)

5.0

11.0

Max. Supply pressure 
(in w.c.)

10.0

14.0

Main Burner Injector

82-580

92-200

Pilot Injector

35

27

By-Pass Screw

185

125

Specifi cations

© 2018 Miles Industries Ltd. All rights reserved.

WARNING

This conversion kit shall be installed by a 
qualifi ed service agency in accordance with 
the manufacturer’s instructions and all appli-
cable codes and requirements of the authority 
having jurisdiction. If the information in these 
instructions is not followed exactly, a fi re, ex-
plosion or production of carbon monoxide may 
result causing property damage, personal in-
jury or loss of life. The qualifi ed service agency 
is responsible for the proper installation of this 
kit. The installation is not proper and complete 
until the operation of the converted appliance 
is checked as specifi ed in the manufacturer’s 
instructions supplied with the kit.

Use this manual in conjunction with the instal-
lation manual supplied with the appliance.

Gas Conversion Kits RA24JBNK / RA24JBPK

Use with 

Valor Retrofi re Heater Models RF24JB ONLY

INSTALLATION & OWNER’S MANUAL

Retro

fi

 re

Natural Gas Burner:
Has two interlaced rows of slots

Propane Gas Burner: marked “LPG”
Has single row of slots and two rows
of small holes

Summary of Contents for Retrofire RF24JB

Page 1: ... 14 0 Main Burner Injector 82 580 92 200 Pilot Injector 35 27 By Pass Screw 185 125 Specifications 2018 Miles Industries Ltd All rights reserved WARNING This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all appli cable codes and requirements of the authority having jurisdiction If the information in these instructions is not f...

Page 2: ...er by removing two nuts using a 5 16 8 mm wrench 8 Replace the main burner with the burner assembly supplied with the conversion kit and reassemble the module 9 Accessing the pilot assembly from the underside of the module disconnect the pilot pipe using a 7 16 11 mm wrench 10 Remove the pilot injector Replace with the appropriate gas injector 11 Remove and replace the minimum rate by pass screw f...

Page 3: ... on the gas supply and check for leaks using a soap solution The minimum and maximum gas supply pressures are shown on page 1 and should be verified using the Supply Pressure test tap while the unit is running at full input 16 Fit a manometer to the manifold pressure test tap on the valve Light the appliance and turn the control to full input Check for leaks downstream of the valve Adjust the press...

Page 4: ...x en c e 10 0 14 0 Injecteur du brûleur principal 82 580 92 200 Injecteur de la veilleuse 35 27 Vis d indice 185 125 Spécifications 2018 Miles Industries Ltd Tous droits réservés AVERTISSEMENT Ce kit de conversion doit être installé par une agence de service qualifiée selon les directives du fabricant et tous les codes et règlements applicables dans la juridiction de l installation Dans les cas ou l...

Page 5: ...lé de 5 16 8 mm 8 Remplacez le brûleur par le brûleur fourni avec la trousse et réassemblez le module du brûleur 9 Accédez à l assemblage de la veilleuse par en dessous de la plaque et débranchez le conduit de la veilleuse à l aide d une clé de 7 16 11 mm 10 Enlevez l injecteur de veilleuse Remplacez le par l injecteur pour le gaz approprié à la conversion selon les spécifications à la page 4 11 En...

Page 6: ... la connexion de vérification de pression pendant que l appareil fourni l apport maximal 16 Branchez un manomètre à la connexion de vérification de la pression d admission Allumez l appareil et tournez le bouton de contrôle pour l apport maximal Vérifiez s il y a des fuites en aval de la valve Réglez la vis de réglage de pression pendant que l appareil fonctionne à son apport maximal afin de produire ...

Reviews: