background image

3

Supply 
pressure
test tapping

Manifold 
pressure
test tapping

Front Face of Control Valve

Pry off
Plastic Cap

Front Face of Control Valve

Pressure Adjustment Screw
behind Cap

Increases Pressure

Decreases Pressure

11. Lever off the small domed cap covering the 

manifold pressure setting screw, on the front face 
of the valve cover by using a screwdriver or similar.

12. Refi t the module and log support to the appliance.

13. Fit the aeration shutter for propane gas set as per 

diagram.

14. Turn on the gas supply and check for leaks using 

a soap solution. The minimum and maximum gas 
supply pressure are 11” and 14” w.c. and can be 
verifi ed using the inlet supply pressure test tapping.

15. Using a small straight blade screwdriver, back off 

the plug screw within the manifold pressure test 
tapping. Fit a manometer to the manifold pressure 
test tapping.

16. Light the appliance and turn up to full fi re. Check for 

leaks downstream of the valve. Adjust the manifold 
pressure setting screw to 10.5” w.c. 

17.  Turn the appliance off. Remove the manometer 

and tighten the test tapping screw. Refi t the domed 
plug.

18. Fit the data conversion label and signed conversion 

label close to the rating plate. Fit the control 
conversion label near the controls.

19. Re-install all ceramics, check that the appliance 

operates correctly. Refer to main instructions.