background image

Supply 
pressure
test tapping

Manifold 
pressure
test tapping

Gas Supply Installation

The gas supply inlet connection is a 3/8” NPT female 

connector and is located on the left hand side of the 

control valve.

Use only new black iron or steel pipes or copper tubing 

if acceptable—check local codes. Note that in USA, 

copper tubing must be internally tinned for protection 

against sulfur compounds.
The burner platform and gas train on this appliance 

may be removed as a unit for servicing or to install or 

remove the optional circulating fan (if installed). Provide 

some form of pipe union (depending on type of piping) 

as close as possible to appliance valve.
Unions in gas lines should be of ground joint type.
The gas supply line must be sized and installed to 

provide a supply of gas sufficient to meet the maximum 

demand of the appliance without undue loss of 

pressure.
Sealant used must be resistant to the action of all 

gas constituents including LP gas. Sealant should be 

applied lightly to male threads to ensure excess sealant 

does not enter gas lines.
Pressure test the supply line for leaks.
The appliance and its individual shut-off valve must be 

disconnected from the gas supply piping system during 

any pressure testing of that system at test pressures in 

excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply 

piping system by closing its equipment shut-off valve 

during any pressure testing of the gas supply piping 

system at test pressures equal to or less than 1/2 psi 

(3.5 kPa).
Failure to either disconnect or isolate the appliance 

during pressure testing may resulting regulator or valve 

damages and void the warranty. Consult your dealer in 

case of damages.

X

Pressure Test Points

The minimum supply pressure is given in the section 

Specifications

 of this manual—page 5.

All piping and connections must be tested for leaks 

after installation or servicing. All leaks must be 

corrected immediately.
When testing for leaks:
•  Make sure that the appliance is turned off.

•  Open the manual shut-off valve.

•  Test for leaks by applying a liquid detergent or soap 

solution to all joints. Bubbles forming indicate a gas 

leak. 

Never use an open flame to check for leaks. 

Correct any leak detected immediately.

The pressure test tapping locations is shown in the 

figure below. An internal regulator within the valve 

controls the burner manifold pressure. The correct 

pressure range is shown in the table in subsection 

Ratings

 of this manual on page 5. The pressure 

check should be made with the burner alight and at its 

highest setting. See 

Lighting Instructions

 section for full 

operating details on page 26.

Pressure Testing

14

Summary of Contents for Legend 739ILN

Page 1: ...ble for installation in a bedroom or bed sitting room Manufactured by MILES INDUSTRIES LTD British Columbia Canada www valorfireplaces com Do not store or use gasoline or other flammable vapors and li...

Page 2: ...l your dealer immediately Do not try to repair the unit as you may cause an injury or damage the fireplace The information contained in this installation manual is believed to be correct at the time o...

Page 3: ...tion 14 Ceramic Bricks Installation 15 Ceramic Logs Installation 15 Window Refitting 17 Remote Control Initial Set up 17 Operation Check Aeration Settings Adjustment 18 Remote Control Handset Wall Hol...

Page 4: ...ration Due to the high temperature the appliance should be LOCATED out of traffic areas and away from furniture and draperies Clothing or flammable material SHOULD NOT BE PLACED on or near the applian...

Page 5: ...h the current ANSI Z223 1 and or local codes having jurisdiction Heating value of gas in some areas is reduced to compensate for elevation consult your local gas utility to confirm For installations a...

Page 6: ...nstall into combustible construction This appliance is NOT APPROVED for installation with a zero clearance kit 739IL fireplace Chimney Terminal Cap Flashing 2 x 3 approved flex chimney liners running...

Page 7: ...tion Electrical inlet Optional Outer Trim or Surround sold separately X Y Dimensions Cavity Check that masonry step does not interfere with install dimensions or vent pipe If mantel is combustible see...

Page 8: ...red or un plastered Non combustible materials Material such as steel iron brick tile concrete or materials that bear the UL mark for zero 0 fire rating Sidewall Clearances Minimum distance from side o...

Page 9: ...for allowable vertical vent termination Venting Table Maximum vertical height 40 ft measured to bottom of termination Minimum vertical height 10 ft measured to bottom of termination Maximum horizontal...

Page 10: ...ce cavity Generally no modifications are allowed to the existing fireplace that will compromise the integrity of the existing fireplace Components that are bolted or screwed on such as dampers or baff...

Page 11: ...ill an access hole of 1 5 inch 38 mm or less through the lower sides or bottom of the firebox The access hole must be plugged with non combustible insulation after the gas supply line has been install...

Page 12: ...place to avoid damage electrical outlet fan cavity Fan installation If the 755CFK Circulating Fan Kit blower is to be installed we suggest that you do it now The fan cavity is accessible from the bac...

Page 13: ...the back of the firebox 3 Apply RTV sealant to the collars on the vent slider and fit the two liners ensuring that the exhaust liner is connected to the identified EXHAUST vent collar Secure with 4 t...

Page 14: ...ting of that system at test pressures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its equipment shut off valve during any pressure testing...

Page 15: ...pack the ceramic logs very carefully to avoid damaging the fragile material Install the logs as shown below Please note that the position of the Logs is critical to insure proper performance of the ap...

Page 16: ...end on the pin located on the rear log Rest its wider end on the the crook in the front left log at an angle of approximately 30 degrees from the center line of the fireplace to allow for the flame t...

Page 17: ...in the window seal Remote Control Initial Set up The receiver and the handset of the remote control sys tem must be initially synchronized before the first use 1 Insert alkaline batteries in the remot...

Page 18: ...ect the temperature sensor located in the remote handset Operation Check Aeration Settings Adjustment Operation Check Turn the fireplace flame up and down using the remote control to confirm that the...

Page 19: ...ion of the surface has the immediate effect of compromising the strength of the glass An emulsion type cleaner is recommended Use a soft damp cloth to apply the cleaner Dry the glass with a soft dry p...

Page 20: ...e appliance uses four 1 5 V AA alkaline batteries for its remote control receiver and one 9 V alkaline battery for its handset Batteries should last one to two seasons depending on usage Removing the...

Page 21: ...batteries you can turn off the appliance with the manual switch located on the right hand side of the valve If the 1265WSK Wall switch is installed and the remote control will not be used remove the b...

Page 22: ...rns automatically to maximum flame height 1 Make sure that the MAN knob on the valve is in ON position 2 Make sure that the switch on the valve is in the I position 3 Press and hold the OFF and large...

Page 23: ...sing either the or buttons Mode Sun Moon TEMP Daytime temperature setting Nighttime temperature setting TIMER Start time setting Stop time setting Flame Height The flame height can be adjusted in the...

Page 24: ...you get up P1 start time and to turn off when you leave for the day P1 stop time Then you can set your fireplace to turn on again at the end of the day P2 start time and to turn off when you go to be...

Page 25: ...kaline batteries NOTE With very low battery the valve shuts off the fire completely This does not happen when the power supply is interrupted CAUTION DO NOT USE a screwdriver or other metallic object...

Page 26: ...the oor If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 3 AUTOMATIC IGNITION g 1 Locate the pilot g 3 inside of rebox at Left H...

Page 27: ...Optional Wall Switch Kit 1265WSK Connector Red Yellow GV60 Wiring Diagram Wiring Diagram 27...

Page 28: ...r 46DVA ADF Co axial to Co linear Adapter 46DVA GCL TM 4CAA 556CLA Co linear to Co axial Adapter 46DVA GK TM 4CTA Aluminum Flexible Liner 3 diameter 2280 Series 3 ACFL NOTE 2 ply liner approved to CAN...

Page 29: ...or air from other household equipment or appliances iii Damage due to chemicals dampness condensation or sulphur in the fuel supply lines which exceeds industry standards i This warranty does not cove...

Page 30: ...t Mount 4000138 28 Pilot Gasket B 4000140 29 Burner Tray 4001676 30 Pipe Valve to Main Burner incl olive nuts 4000065 31 Burner Plate Access Panel 4001680 32 Module Gasket Rear 4000175 33 Module Gaske...

Page 31: ...NG LPG 18 20 25 21 22 23 24 19 49a 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 44 43 45 62 63 64 65 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 14a NG...

Page 32: ......

Page 33: ...39IL NG natural gas LPG propane Serial No Front Trim code description e g 743FVI Double Door FenderFire Purchase date mm dd yyyy Home Owner Name Address City Province State Postal Code Zip Phone Email...

Page 34: ...Product Postage needed Were you given all documentation and manuals for your product YES NO Miles Industries Ltd 190 2255 Dollarton Highway North Vancouver BC V7H 3B1 Canada Fold here Online Warranty...

Reviews: