20
Horizontal Termination Venting Con
gurations
See venting accessories list on pages 40–41 for allowable components.
Rear Outlet—No Vertical Rise
Flat on the Wall
• Maximum 26” horizontal pipe length;
• 817VAK Vent Collar Adapter required if using other
than Valor’s 551DVK pipe with termination;
• A Terminal Guard such as 845TG is required where
the vent terminal is located within 7’0” of grade or
where accessible.
In Corner—No Vertical Rise
• Maximum 1 x 45° elbow allowed;
• Maximum 18” horizontal pipe length;
• A Terminal Guard such as 845TG is required where
the vent terminal is located within 7’0” of grade or
where accessible.
Approved
trough wall
shield/thimble
Approved
side wall
termination
530
engine
Max. 26” (66 cm)
14” (36 cm) max.
within
combustible wall.
26” (66 cm) max.
vent length
Use 845TG vent
guard with a
vent terminal
located at less
than 7’ (2.13 m)
above grade
Approved
through wall
shield/thimble
Approved
side wall
termination
530
engine
18” (46 cm)
max vent pipe
QUALIFIED
INSTALLER