Valor 530ILN Installation & Owner'S Manual Download Page 15

15

State of Massachusetts Carbon Monoxide 
Detector/Vent Terminal Signage 
Requirements

For all side wall horizontally vented gas fueled 
equipment installed in every dwelling, building or 
structure used in whole or in part for residential 
purposes, including those owned or operated by the 
Commonwealth and where the side wall exhaust 
vent termination is less than seven (7) feet above 

 nished grade in the area of the venting, including 

but not limited to decks and porches, the following 
requirements shall be satis

 ed: 

1. INSTALLATION OF CARBON MONOXIDE 
DETECTORS. At the time of installation of the side wall 
horizontal vented gas fueled equipment, the installing 
plumber or gas 

 tter shall observe that a hard wired 

carbon monoxide detector with an alarm and battery 
back-up is installed on the 

 oor level where the gas 

equipment is to be installed. In addition, the installing 
plumber or gas 

 tter shall observe that a battery 

operated or hard wired carbon monoxide detector 
with an alarm is installed on each additional level of 
the dwelling, building or structure served by the side 
wall horizontal vented gas fueled equipment. It shall 
be the responsibility of the property owner to secure 
the services of quali

 ed licensed professionals for the 

installation of hard wired carbon monoxide detectors.

a. In the event that the side wall horizontally vented 
gas fueled equipment is installed in a crawl space or 
an attic, the hard wired carbon monoxide detector with 
alarm and battery back-up may be installed on the next 
adjacent 

 oor level.

b. In the event that the requirements of this subdivision 
can not be met at the time of completion of installation, 
the owner shall have a period of thirty (30) days 
to comply with the above requirements; provided, 
however, that during said thirty (30) day period, a 
battery operated carbon monoxide detector with an 
alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. 
Each carbon monoxide detector as required in 
accordance with the above provisions shall comply 
with NFPA 720 and be ANSI/UL 2034 listed and IAS 
certi

 ed. 

Commonwealth of Massachusetts

3. SIGNAGE. A metal or plastic identi

 cation plate 

shall be permanently mounted to the exterior of the 
building at a minimum height of eight (8) feet above 
grade directly in line with the exhaust vent terminal for 
the horizontally vented gas fueled heating appliance 
or equipment. The sign shall read, in print size no less 
than one-half (1/2) inch in size, ““GAS VENT DIRECTLY 
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS””.

4. INSPECTION. The state or local gas inspector of 
the side wall horizontally vented gas fueled equipment 
shall not approve the installation unless, upon 
inspection, the inspector observes carbon monoxide 
detectors and signage installed in accordance with the 
provisions of 248 CMR 5.08(2)(a)1 through 4. 

(b) EXEMPTIONS: The following equipment is exempt 
from 248 CMR 5.08(2)(a)1 through 4: 

1. The equipment listed in Chapter 10 entitled 
““Equipment Not Required To Be Vented”” in the most 
current edition of NFPA 54 as adopted by the Board; 
and 

2. Product Approved side wall horizontally vented 
gas fueled equipment installed in a room or structure 
separate from the dwelling, building or structure used in 
whole or in part for residential purposes. 

(c) MANUFACTURER REQUIREMENTS - GAS 
EQUIPMENT VENTING SYSTEM PROVIDED. 
When the manufacturer of Product Approved side 
wall horizontally vented gas equipment provides a 
venting system design or venting system components 
with the equipment, the instructions provided by the 
manufacturer for installation of the equipment and the 
venting system shall include:

1. Detailed instructions for the installation of the venting 
system design or the venting system components; and

2. A complete parts list for the venting system design or 
venting system. 

QUALIFIED 
INSTALLER

Summary of Contents for 530ILN

Page 1: ...cinity of this or any other appliance Installation and service must be performed by a qualified installer service agency or the gas supplier Ce guide est disponible en fran ais sur demande This applia...

Page 2: ...F O R T V A LOR CO M F O R T V A LOR CO M F O R T Commonwealth of Massachusetts 15 Speci cations 17 Dimensions Clearance and Framing 18 Horizontal Termination Locations 19 Horizontal Termination Venti...

Page 3: ...and draperies Clothing or ammable material SHOULD NOT BE PLACED on or near the appliance Clothing or ammable material SHOULD NOT BE PLACED on or near the appliance This unit MUST be used with a vent s...

Page 4: ...e A physical barrier is strongly recommended if there are young children or at risk individuals in the house Install an approved after market safety gate to keep toddlers young children and other at r...

Page 5: ...th or oor The hearth or oor in front of the replace may become very hot in front of the replace may become very hot when the replace heats Do not use the hearth when the replace heats Do not use the h...

Page 6: ...ting If broken the glass pane may only be replaced as a complete window unit as supplied by the manufacturer If the barrier becomes damaged the barrier shall be replaced with the manufacturer s barrie...

Page 7: ...alve using the manual On Off switch see instructions on next page The appliance uses four 1 5 V AA alkaline batteries for its remote control receiver and one 9 V alkaline battery for its handset The b...

Page 8: ...l override the wall switch Wall Switch optional Remote control handset Valve Switch ON OFF O O How to Turn Your Fireplace OFF including pilot Familiarize yourself with each of these methods before ope...

Page 9: ...height NOTE Before using the remote control system for the first time the receiver and the handset must be synchronized See the section Remote Control Initial Set up on page 36 of this manual Set scr...

Page 10: ...s small ame button to set the minute Press OFF or simply wait to return to MAN mode Double click large ame button Flame automatically goes to high re HI will be displayed Manual Mode Manual Flame Heig...

Page 11: ...programming SETTING THE DAYTIME TEMPERATURE SETTING THE NIGHTTIME SETBACK TEMPERA TURE Default Settings sun 23 C 74 F Default Settings moon OFF Press large ame button to increase Nighttime Setback Te...

Page 12: ...l to TIMER moon while the time ashes Press large ame button to set the hour Press large ame button to set the hour Press small ame button to set the minutes Press small ame button to set the minutes S...

Page 13: ...oes not apply when the power supply is interrupted No change in pilot The appliance shuts off completely when it is continually in pilot position without any change for a period of 5 days Timer Progra...

Page 14: ...r If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 3 AUTOMA7 1 7 21 J RFDWH WKH SLORW J LQVLGH RI UHER DW HIW DQG VLGH 21 2 VZLWF...

Page 15: ...attery operated carbon monoxide detector with an alarm shall be installed 2 APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions shall c...

Page 16: ...instructions shall be included with the appliance or equipment installation instructions and 2 The special venting systems shall be Product Approved by the Board and the instructions for that system...

Page 17: ...anada please consult provincial and or local authorities having jurisdiction NG LPG Altitude Ft 0 4500 Input Max Btu h 20 500 19 000 Input Min Btu h 6 500 12 500 Manifold pressure in w c 3 5 3 9 10 3...

Page 18: ...the hot when the fireplace heats Do not use the hearth as a seat or shelf Solid wood flooring hearth as a seat or shelf Solid wood flooring in front of the fireplace if allowed may in front of the fir...

Page 19: ...center line of meter regulator assembly located within 15 feet 4 6 m below the terminal 36 90 I Clearance to service regulator vent outlet 36 90 J Clearance to non mechanical air supply inlet to the b...

Page 20: ...or where accessible In Corner No Vertical Rise Maximum 1 x 45 elbow allowed Maximum 18 horizontal pipe length A Terminal Guard such as 845TG is required where the vent terminal is located within 7 0...

Page 21: ...here the vent terminal is located within 7 0 of grade or where accessible 14 36 cm max combustible wall Approved side wall termination Approved through wall shield thimble 530 engine Use 845TG vent gu...

Page 22: ...es not penetrate the inner pipe Secure the vent unit or 817VAK to the outer collar with two no 6 thread cutting screws supplied Through the wall details If the wall has combustible material appropriat...

Page 23: ...n the particular installation 1 5 16 33 mm min clearance to combustible materials all round 40 12 2 m max Total offset 4 6 137 cm max Ceiling firestop Roof flashing Approved vertical termination 8 2 4...

Page 24: ...le construction The appliance must not be connected to a chim ney ue serving a separate solid fuel burning appliance Flashing 2 x 3 liners 24 1 2 3 min bend radius Co linear adapter 2 x 3 liners 18 ma...

Page 25: ...ace the appliance in its proper location 3 Drop a plumb from the ceiling to the center of the appliance vent opening Mark the position on the ceiling Drill a small hole at the marked position 4 Determ...

Page 26: ...l run as shown on page 24 in this manual 5 Fit the termination kit and ashing if required to the exterior of the chimney 6 Secure the appliance to the oor or wall if necessary Vertical Termination Ins...

Page 27: ...collar and seal by unscrewing 8 screws 4 To make sure that the collars are axially aligned t the adapter 817VAK over the outer vent collar 5 Position the inner collar and seal vertically inside the t...

Page 28: ...to the outer collar with two no 6 thread cutting screws supplied Co linear Conversion using Valor 556CLA Co linear Adapter Note Instructions may vary as 556CLA may be installed on Top or Back of Heate...

Page 29: ...table below to nd out which position is optimal for each type of installation To t the restrictors loosen the two center screws of the left and right inlet ports Place the restrictor assembly under t...

Page 30: ...must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5kPa The appliance must be isolated from the gas supply pip...

Page 31: ...ine see Ceramic Rocks Installation section in this manual At this point you can install the 567FGP Top Grille if used logs or rock version only The 567FGP Top Grille is sold separately except with the...

Page 32: ...5 1 2 3 Burner SIDE VIEW Back Brick Burner bracket Rest the base log behind the burner on its bracket flange BASE LOG Firebox supports 1a 5 Locate the left side log on the ceramic pin on the left han...

Page 33: ...front coal behind the metal lip at the front of the rebox Its left side should rest over the projection on the left front coal 1 2 4 5 3 1a Burner SIDE VIEW Back Brick Burner bracket Rest the base co...

Page 34: ...arately fit it now See instructions supplied with the grille 3 Place the rear panel on the rear support as indicated Hold in place and go to next step 4 Place the left and then the right panels in the...

Page 35: ...ocks L and R Those rocks don t have any peg or hole Install those rocks as indicated at the left and right of the rock pile positioning them so that the arrows underneath point to the front of the rep...

Page 36: ...ween the glass and the frame as indicated Remote Control Initial Set up The receiver and the handset of the remote control sys tem must be initially synchronized before the rst use 1 Insert alkaline b...

Page 37: ...may be improved by adjusting the aeration The need for adjustment should be determined only by operating the appliance with the ceramic rocks and window installed Increasing aeration will cause the a...

Page 38: ...holder to the wall nd a convenient location and use the hardware provided with the kit See the diagram on the right for required hardware and con gurations Note that the holder can be installed at the...

Page 39: ...39 Wiring Diagram Optional Wall Switch Kit 1265WSK Connector Red Yellow GV60 Wiring Diagram QUALIFIED INSTALLER...

Page 40: ...DSC V Co linear Flex Connector 46DVA ADF Co axial to Co linear Adapter 46DVA GCL TM 4CAA 4DCAB33 556CLA Co linear to Co axial Adapter 46DVA GK TM 4CTA 4DCAT33 Aluminum Flexible Liner 3 diameter NOTE 2...

Page 41: ...Flashing TF 4MF Various Venting System Parts Wall Thimble 46DVA WT 4DT WT TM 4WT SV4RSM 4DWT Storm Collar 46DVA SC 4DT SC TM SC SV4AC 4DSC Decorative Plate 46DVA DC 4DT CS TM 4TR SV4PF 4DFPB Cathedra...

Page 42: ...r from other household equipment or appliances iii Damage due to chemicals dampness condensation or sulphur in the fuel supply lines which exceeds industry standards i This warranty does not cover gla...

Page 43: ...pport 320B399 41 Switch bracket 4001070 41a Switch with cable 4001036 41b Cable interruptor receiver 4001035 42 Interruptor block 4001037 43a GV60 Valve NG 4003094 43b GV60 Valve LPG 4003107 Code Desc...

Page 44: ...1 2 4 5 6 7 8 9 10 11 12 13 14 19 20 21 22a 22b 23 24 25 26 27 28 29 30 31 33 32 34 35 36 38 39 40 41 42 44 43a 43b 45 46 47 48 41a 41b NG LPG 16a 16b 15a 15b Replacement Parts 44a 49 OWNER S INFORMAT...

Page 45: ...45 51 52 53 54 55 56 57 58 59 60 61 62 63 50 Replacement Parts 64 65 66 67 69 73 71 74 72 75 76 77 78 79 80 81 70 68 For 530IRN P only For 530ILN P and ICN P OWNER S INFORMATION...

Page 46: ......

Page 47: ...rovided will be used for customer records only Online Warranty registration at www valorfireplaces com Cut out page ll information and mail to Miles Industries Ltd Fireplace Information Model Number 5...

Page 48: ...hut Thank you for choosing a Valor Product Postage needed Miles Industries Ltd 190 2255 Dollarton Highway North Vancouver BC V7H 3B1 Canada Fold here Online Warranty registration at www valorfireplace...

Reviews: