background image

VALLOX DIGIT2 SE/VKL/MLV

Code

Name

Technical data

(factory settings in parentheses)

Standard/

Option

Code

Name

Technical data

(factory settings in parentheses)

Standard/

Option

CO

2

Carbon dioxide sensor

Adjustment range 500…2000 ppm (900)

Option

Carbon dioxide control

Adjustment interval 1…15 min. (10)

G3

Filter

Supply air, extract air

Standard

F7

Filter

Supply air

Standard

PM

Damper motor

Automatic HR bypass, 24 V, 0.5 W, 2 Nm

Standard

H

Control panel

User interface

Standard

R2

Preheating unit

Liquid radiator

Standard

R1

Post-heating unit

a) Water radiator (Digit2 SE MLV VKL)

Standard

b) Electric radiator 1.2 kW 

Standard

    (Digit2 SE MLV electric)

HR

Heat recovery cell

Cross-counter flow, efficiency = 60%

Standard

P1

Pressure difference switch

Adjustment range 0...500 Pa (320)

Option

Pressure guard on the supply
air side

P2

Pressure difference switch

Adjustment range 0...500 Pa (320)

Option

Pressure guard on the extract
air side

E

Extract air fan AC

qv = 120 dm

3

/s (120 Pa)

Standard

%RH

Humidity sensor

Automatic/ Adjustment range 1...99% (99) 

Option

Humidity control

Adjustment interval 1…15 min. (10) (10)

© VALLOX • We reserve the right to make changes without prior notification.

17

PART LIST

Parts list VALLOX DIGIT2 SE (heating/cooling radiator model)

TE1

Temperature sensor

Exhaust air temperature

Standard

HR antifreeze

Adjustment range -6...+15 

°

C (HR)

TE2

Temperature sensor,

Supply air temperature

Standard

precooling control

Adjustment range +10…30 

°

C

TE3

Temperature sensor,

Outdoor air temperature

Standard

preheating control

Adjustment range -6…15 

°

C (preheating) 

TE4

Temperature sensor

Extract air temperature

Standard

TS1

Overheat protector for

Aut40 

°

C

Included in 

the heating unit

R1

TS2

Overheat protector for

Manually reset, +80 

°

C

Included in

the heating unit

 

R1

S

Supply air fan AC

qv = 100 dm

3

/s (100 Pa)

Standard

V

Water radiator actuator/valve

Standard

MV

Solenoid valve

Not included
in the delivery

KP

Circulation pump

Not included
in the delivery

TK

Fireplace/booster switch function In the controller

Standard

Either fireplace or
booster switch function

Separate switch

Option

SP

Damper 2 pcs

Air flow operated

Standard

LON

LON converter

Remote monitoring control

Option

Summary of Contents for Digit 2 SE Series

Page 1: ...Preheating unit MLV liquid radiator Post heating unit Electric 1200 W 5 2 A Filters Supply air G3 and F7 Extract air G3 Weight 71 kg Ventilation Control panel control adjustment options Week clock co...

Page 2: ...panel CO2 sensor option LON converter option Air flow measuring outlets behind cover plate Water radiator actuator valve Connection 12 MLV connection 10 cu 20 21 Supply air to the dwelling Extract air...

Page 3: ...plate You can measure the total pressure of the supply and extract air ductwork at the measurement outlets using a pressure gauge Compare the pressure readings with the air volume curves to see unit a...

Page 4: ...7 38 9 31 5 68 0 50 1 66 3 62 9 55 4 46 7 45 0 42 3 34 4 24 3 68 2 52 5 64 1 63 4 59 9 48 7 46 8 45 0 37 1 26 5 69 1 54 2 70 2 65 2 60 0 50 6 48 1 47 1 39 2 32 5 71 8 56 1 70 4 66 9 62 2 52 9 50 2 49...

Page 5: ...dicator is not lit 1 2 3 4 5 6 7 8 Fan speed 3 Supply air temperature 21 C Post heating is on Time Filter guard alert Maintenance reminder alert Fireplace booster switch on The fireplace booster switc...

Page 6: ...nnect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the 6K8resistor in the termi nal block remove the resistor in this ca se and the seco...

Page 7: ...dB LWA dB A 1 16 24 2 25 47 3 36 70 4 48 90 5 58 104 6 68 116 7 75 131 8 87 148 1 25 7 2 38 7 3 46 46 4 59 69 5 72 79 6 82 106 7 92 112 8 104 141 LpA dB A AP qV dm3 s AP supply extract dm3 s ED and SD...

Page 8: ...WITCH REMOTE MONITORING 1 10 2 3 4 5 6 7 8 9 1 10 16x0 25mm2 1 2 A 2 3 4 REMOTEMONITORING 0 10VDCor0 20mA ha ro L 6 7 FIREPLACESWITCH 6 va vi va ke R ke r r vi 7 5 7018800 2 1 N K K 1 2 r s m r 2N 1 2...

Page 9: ...SENSOR IS CONNECTED TO REPLACE THE R6k8 RESISTOR HUMIDITY SENSOR RH1 OPTION BLACK M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1 FAULT SIGNAL MAX 1 A 24 VDC POTENTIAL FREE CONTACTS FIREPLACE SWITCH pressure...

Page 10: ...e loss in the valve 0 3 0 4 Liquid flow dm3 s 0 2 0 02 0 03 0 04 0 05 0 06 0 08 0 1 0 01 1 2 3 4 5 6 7 0 25 0 5 0 75 1 00 1 25 1 45 1 55 1 7 17 5 open Adjustment position Kv value Pressure loss p kPa...

Page 11: ...s 70 dm3 s 90 dm3 s 8 10 Radiator pressure loss kPa 10 5 15 20 25 0 0 06 liquid flow dm3 s 30 0 08 0 04 0 02 0 35 Performance of VALLOX DIGIT2 SE MLV heating cooling radiator MLV RADIATOR HEATING POWE...

Page 12: ...out prior notification CONTROL DIAGRAM ELECTRIC RADIATOR 12 Parts list VALLOX DIGIT2 SE electric radiator model TE1 Temperature sensor Exhaust air temperature Standard HR antifreeze Adjustment range 6...

Page 13: ...henever outdoor air temperature falls below the threshold set or when outdoor air is warmer than extract air Heat recovery antifreeze The control centre of the unit controls the operation of preheatin...

Page 14: ...reserve the right to make changes without prior notification CONTROL DIAGRAM VKL MODEL 14 Parts list VALLOX DIGIT2 SE VKL water radiator model TE1 Temperature sensor Exhaust air temperature Standard H...

Page 15: ...e sensors TE1 and TE3 preventing the risk of freezing and the intermittent stopping of supply air fan S If the power of preheating unit R2 is not enough or is not on the control centre intermittently...

Page 16: ...TION PANEL PLUG LON CONVERTER REMOTE MONITORING CONTROL CENTRE OF THE PROPERTY ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT VENTILATION ZONE INTERNAL ELECTRICAL AND CONTROL CONNECTIONS POST HEA...

Page 17: ...sensor Automatic Adjustment range 1 99 99 Option Humidity control Adjustment interval 1 15 min 10 10 VALLOX We reserve the right to make changes without prior notification 17 PART LIST Parts list VAL...

Page 18: ...very antifreeze Controlling preheating in a liquid circulating MLV radiator is different from that in an electric preheating radiator The liquid radiator switches on based on the measurement data from...

Page 19: ...straight The outdoor air duct must be insulated against condensation also between the unit and the ceiling mounting plate Installation Lift the unit straight upwards till the locking wings on the sid...

Page 20: ...ivery Because of the risk of condensing the pump should be suitable for pumping liquid colder than the ambient temperature e g Grundfors UPS 25 60 180 model K MV Solenoid valve not included in the del...

Reviews: